Eltek Rectifier Module Flatpack2 48/2000 He (PART NO. 241115.105)

Price $0.20 Compare
Min Order 1 Piece
Shipping From Hubei, China
Popularity 308 people viewed
Quantity
+-
 

Wuhan Unique Mechanical & Electrical Equipment Co., Ltd.

VIP   Audited Supplier 5 years
Profile Certified by SGS/BV
FLATPACK2 48/2000 HE
Telephone, Computer, Workstation, Server
Wired
Ethernet
Data
CE, ISO, RoHS
New
1.950 Kg [4.3lbs]
109X41.5X327mm
Eltek
Plywood Case
Brand New
Wuhan
8504409190
Product Description

Short Description:

 

The combination of innovative design, efficiency and reliability makes the Flatpack2 HE stand out.

Increasing network speed demands flexible and expandable DC power solutions. The Flatpack2 HE rectifiers are your key building blocks for future needs.

With an efficiency up to 96.5%, the losses have been reduced by 50% compared to the current industry standard. In a global perspective, considering the high energy consumption in the telecom industry, this technology breakthrough is not only reducing operational cost for the operators, but it can also have a significant environmental impact.

 

Applications

Telecom - mobile / wireless
•radio base stations/ cell sites
•lte / 4g / wimax
•mobile switching center (msc)
•microwave
•broadband telecom - fixed
•central office
•telephony servers / switches
•fiber optics
•microwave
•broadband
•datacenters 
power utilities
•scada

Key features 
•proven reliability
•high efficiency (he)
•power dense, up to 33 w/inch3
•wide temperature range
•application flexibility 2kw
•global compliance (ce, ul)
•patented he technology

Flatpack2 48v he rectifiers doc 24111x.105.Ds3 - v6.1

Model48V / 2000W HE48V / 3000W HE
Part number241115.105241119.105
INPUTDATA
Voltage (nominal)185 - 275 VAC / 185 - 275 VDC176 - 277 VAC
Voltage (range)85 - 300 VAC / 85 - 275 VDC85 - 305 VAC
Frequency45 - 66 Hz, 15-18.5 Hz1) / 0 Hz45 - 66 Hz
Current (maximum) @ nominal input, full load11.6 ARMS19.2 ARMS
ProtectionFuse in both lines Varistor for transient protection Disconnect above 300 VAC/DCFuse in both lines Varistor for transient protectionDisconnect above 305 VAC
OUTPUT DATA
Voltage (default)53.5 VDC
Voltage (adjustable range)43.5 - 57.6 VDC43.5 - 583) VDC
Power (maximum)2000 W3000 W
Power @ 85 VAC850 W1380 W
Current (maximum) @ nominal input, full load41.7 A62.5 A
Ripple, 30MHz bandwidth< 100 mVpp< 150 mVpp
Psophometric noise< 2 mVRMS< 2 mVRMS
Static Voltage regulation±0.5% for 10 - 100% load
Dynamic Voltage regulation±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
ProtectionFuse, Short circuit proof, High temperature protection, Hot plug-in inrush current limiting
OTHER SPECIFICATIONS
Efficiency @ nominal input96 %
Isolation3.0 kVAC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth
Alarms: Red LED 'on'Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings: Yellow LED 'on'Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage
Normal (module running): Green LED 'on'
Acoustic noise, full load @ Tambient = 25°Cfull load @ Tambient = 40°C< 20 dBA< 56 dBA< 40 dBA< 58 dBA
MTBF (Telcordia SR-332 Issue I method III (a))>350 000 (@ Tambient : 25 °C)>300 000 (@ Tambient : 25 °C)
Operating temperature-40 to +75°C (-40 to +167°F)4), humidity 5 - 95% RH non-condensing
Temperature de-rating>55°C (131°F), 1200W @ 75°C (167°F)>55°C4) (131°F), 2100W @ 75°C (167°F)4)
Storage temperature-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight109 x 41.5 x 327mm (4.25 x 1.69 x 13") / 1.95 kg (4.3 lbs)
DESIGN STANDARDS
Electrical safetyEN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014, CSA C22.2 No.60950-1-07:2014, IEC 60950-1:2013
EMCEN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019, EN 61000-3-2:2019 ETSI EN 300 386 V.2.1.1, Telcordia NEBS GR1089 CORE
MarineDNVGL-CG-03392)-
 EnvironmentETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE)Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised
power derating, maximum 1000W @ 230Vac 16 2/3 Hzonly valid for part number 241115.105M57.6V for HW revision ≤ 5 from HW revision 6: shutdown at 95°C with de-rating to~1000W 
 

Hotsale Modules

1Rectifier moduleEmerson /VertivR48-1800A
2Rectifier moduleEmerson /VertivR48-2000A3
3Rectifier moduleEmerson /VertivR48-2900U
4Rectifier moduleEmerson /VertivR48-3000e3
5Rectifier moduleEmerson /VertivR48-3500e
6Rectifier moduleEmerson /VertivR48-5800A
7Rectifier moduleHuawiR4850N1
8Rectifier moduleHuawiR4850G1
9Rectifier moduleEltekFlatpack2 48/2000 HE
241115.105
10Rectifier moduleEltekFlatpack2 48/1000 HE
241122.105
11Rectifier moduleEltekFlatpack2 48/3000 HE
241119.105
12Rectifier moduleEatonAPR24-3G