ExS6061SF-05/10/15DFK-1
ISO, CE
AC DC24V AC230V
Electric Power
Ordinary Temperature
SOLOON
Cartons
China
Product Description
ExS6061SF-05/10/15DFK-1/24(230)V
Model Para. | ExS6061SF-05DFK-1/24V | ExS6061SF-10DFK-1/24V | ExS6061SF-15DFK-1/24V | ExS6061SF-05DFK-1/230V | ExS6061SF-10DFK-1/230V | ExS6061SF-15DFK-1/ 230V | |
Torque | 5Nm; 10Nm; 15Nm | ||||||
Damper Size | 1m2; 3m2; 4.5m2 | ||||||
Power Supply | AC230V AC24V DC24V 50/60Hz i ≤0.2A AC220V 50/60Hz | ||||||
Consumption | 7W run/3W remain;10W run/3W remain;12W run/3W remain | ||||||
Wire Size | 10VA | ||||||
Connection cable | Power:1m cable 3*0.5 m2 | ||||||
Auxiliary Switch (F):1m cable 6*0.5 m2 | |||||||
Running Time | Motor≤15s;Spring Return≤1s | ||||||
Angle of Rotation | Max 93º | ||||||
Position Indication | Mechanical indicator | ||||||
Weight | 5Kg | ||||||
Life Cycle | ≥1000 cycles | ||||||
Sound Level | 50dB(A)and62dB(A) | ||||||
IP Protection | IP66 | ||||||
Temperature | -20~+60ºC | ||||||
Ambient Temperature | 5~95%RH | ||||||
Explosion-proof Mark | Ex db B T6 T5 Gb Ex tb IIIC T85°C Db -20ºC≤Ta≤+55ºC (T6) -20ºC≤Ta≤+60ºC (T5 and T85ºC) |
Features:
- Single control
- Form-fit 12x12 shaft
- Universal shift plug
- Two auxiliary switches
- Cast aluminum housing, compacting type
- Safety meets IP66
- IEC60079-0:2017, EN60079-0:2018 electrical apparatus in explosive gas atmosphere - part0: General requirements.
- IEC60079-1:2014, EN60079-1:2014 electrical apparatus in explosive gas atmosphere - part1:flameproof"d".
- IEC60079-31:2013,EN60079-31:2014 explosive atmospheres part31: Equipment dust ignition protection by enclosure "t".
- Cable connector and the housing mating thread size M16 × 1.5, cable diameter size Φ6-Φ8. When the equipment is used on site, the cable gland should be installed by user, whose protection grade should not be lower than 2D Ex tb IIIC T85°C Db.
- Within ground terminal tightening torque 2N.m.
- Flameproof joint tightening torque is 3.2N.m.
- External ground bolt M4X6, pressing 4mm² conductor.
- The entry shall be equipped with Ex certified cable glands with a compatible mode of protection for the intended use.
Maintenance:
- When assembly, operation and maintenance, the operator should follow the requirements of EN 60079-14, beside of the instruction manual.
- Repair and overhaul shall comply with EN 60079-19.
- The product shell is cleaned with wet cloth and the user is forbidden to repair and modify the flameproof content.
- Disassembly is prohibited without permission Do not open with power. please do not open the cover in the explosive gas. Need to use a damp cloth when opening.l
- AFTER DE-ENERGIZING, DELAY 10 MINUTES BEFORE OPENING.
- DO NOT OPEN WHEN ENERGIZED.
- POTENTIAL ELECTROSTATIC HAZARD - SEE INSTRUCTIONS.
- USE FASTENERS WITH YIELD STRESS >=450MPa
- The flame-proof joints cannot be repaired or modified by user.
- Installation must be carried out by personnel with relevant training or working experience. During installation,pls do not operate with electric and in accordance with the regulations.
- There are electrical and electronic parts in the device, so it is forbidden to disposal as ordinary garbage after the product is scrapped. The disposal method should comply with the local government's regulations and requirements.
Electrical connection and out line:

Description of product function and application:
- Explosion-proof electrical appliances refer to a class of electrical equipment used in places where explosive gases and vapors exist.
- Coal, petroleum, chemical, textile and other industries in the national economy occupies a very important position, these industries in the production process will produce explosive gas.Steam or explosive dust, such places are called explosive dangerous places.
- Our company produces the explosion-proof type air valve actuator as part of the not mine explosion-proof electrical equipment. 90% of mine explosion-proof electrical equipment is used in oil, chemical, pharmaceutical and other industries) (hereinafter referred to as petrochemical industry, inflammable and explosive gas/steam is common and combustible dust existing environment/work sites and at the same time.
Special condition of use:
- The flame-proof joints cannot be repaired or modified by user.
- The entry shall be equipped with Ex certified cable glands with a compatible mode of protection for the intended use.
- When assembly, operation and maintenance, the operator should follow the requirements of EN 60079-14, beside of the instruction manual.
- Repair and overhaul shall comply with EN 60079-19.