CM1
Low Voltage Circuit Breakers
Electric Type
High-Speed Circuit Breaker
Air
Fixed
MCCB
3
Circuit Breaker
Circuit-Breaker Failure Protection, Overcurrent Protection
ISO9001-2000, CE
MCCB
63A,100A,225A,250A,300A,400A,630A,800A
Negotiable
Factory
CE/ISO9001
Within 1000PCS for 15days
Available
OEM
Carton
China
8536200000
Product Description
Application
RM1(CM1) series MCCB is mainly used in the circuit of AC 50/60Hz,rated insulating voltage 690V ,rated working voltage up to 690V,and rated current from 10A-800A in distribution line for distributing power,protecting line,overload,short-circuit and under-voltage protection. It also can be used for infrequently starting of motor for overload,short-circuit and under-voltage protections.
It is small size,high breaking capacity and short arcing (without arcing).
The products can be installed vertically and horizontally.And it have front connection,rear connection and plug-in connection.
The product meets the standards of GB14048.2 and IEC60947-2.
The product meets the standards of GB14048.2 and IEC60947-2.
Normal Working Condition
Altitude: not exceed 2000m
Ambient air temperature:
1) Temperature: -5° C---+ 40° C
2) 24 hours average air temperature shall not exceed + 35° C
3) If the air temperature is more than + 40° C, it need remark the special ordering.
Air conditions:
At mounting site,relative humidity not exceed 50% at the max temperature of +40° C,higher relative humidity is allowable under lower temperature.For example,RH could be 90% at +20° C,special measures should be taken to occurrence of dews.
Pollution grade:Grade 3
Protection Grade: IP20







Circuit Breaker Specification:
Frame class Rated current InmA | Conventional Rated heat current Ith A | Rated current A | Short circuit breaking capacity class | Short circuit breaking capacity kA(Effective value) Icu/Ics | |
AC 400V | AC 690V | ||||
63 | 63 | 10,16,20,25,32,40,50,63 | L | 25/18 | / |
M | 50/35 | / | |||
H | 85/50 | / | |||
125(100) | 125(100) | 16,20,25,32,40,50,63,80,100,125 | C | 25/18 | 10/5 |
L | 35/22 | 10/5 | |||
M | 50/35 | 20/10 | |||
H | 80/50 | 20/10 | |||
250(225) | 250(225) | 100,125,140,160,180,200,225,250 | C | 25/18 | 10/5 |
L | 35/22 | 10/5 | |||
M | 50/35 | 20/10 | |||
H | 80/50 | 20/10 | |||
400 | 400 | 225,250,315,350,400 | L | 50/35 | 10/5 |
M | 65/42 | 20/10 | |||
H | 100/65 | 20/10 | |||
630 | 630 | 400,500,630 | L | 50/35 | 10/5 |
M | 65/42 | 20/10 | |||
H | 100/65 | 20/10 | |||
800 | 800 | 630,700,800 | M | 65/50 | 30/15 |
H | 100/65 |
Circuit Breaker Tripping Characteristics:
Rated current of release (A) | Thermodynamic release(ambient temp+40) | Operational current of magneticrelease (A) | |||
1.05In(cold state) inoperative time (h)
| 1.I3n 0h(eat state)inoperative time(h) | ||||
In<63 | ≥1 | <1 | 10In±20% | ||
63<In<100 | ≥2 | <2 | 10In±20% | ||
100<In<630 | ≥2 | <2 | 5-10In±20% | ||
Rated current of release (A) | Thermodynamic release(ambient temp+40ºC) | ||||
1.0In (cold state) | 1.20In (heat state) | 1.50In (heat state) | 7.2In (heat state) | Operational current of magnetic release (A) | |
12.5<In<400 | ≥2h | <2h | <4min | 2S<Tp<10s | 12In±20% |