ARSM16-12 630-20 25
VDE, CCC, ISO9001
Stainless Steel
High Voltage
Removable
Cabinet
DC
50Hz
12 Kv
Enclosure IP4X
Ampower
Export Standard Wooden Case
1400*2200*2600/customized
China
Product Description




1. Product Overview
ARSM16-12/24 Sulfur Hexafluoride Fully Insulated Compact Metal Enclosed Switchgear (hereinafter referred to as Sulfur Hexafluoride Inflatable Cabinet) is a ring net cabinet suitable for three-phase AC power system with rated voltage of 12/24 kV and rated frequency of 50/60 Hz. All components are subject to modular design, with flexible configuration and expansion scheme, compact product structure, comprehensive distribution automation scheme, control, segmentation, transformation and protection of lines.It is suitable for areas with large power supply load and high density, such as residential areas, production, power supply, large public buildings, switching stations, industry and commerce, villages and towns, etc. It has the advantages, such as safe use, no wind and rain, convenient installation, locality, less maintenance, high reliability and high utilization rate.
This series of ring net cabinets are mainly designed according to GB3906, IEC298, IEC62271-1 and IEC62271-200.
2. Normal Use Conditions
No. | Name | Unit | Normal use value | |
1 | Ambient air temperature | Maximum air temperature | ºC | +55 |
Minimum air temperature | -40 | |||
Maximum daily temperature difference | K | 25 | ||
2 | Altitude | m | ≤2000 | |
3 | Solar radiation intensity | W/cm2 | 0.1 | |
4 | Pollution level | d | ||
5 | Covered ice thickness | mm | 10 | |
6 | Wind speed/wind pressure | m/s/Pa | 34/700 | |
7 | Humidity | Average daily relative humidity | % | ≤95 |
Average monthly relative humidity | ≤90 | |||
8 | Earthquake resistance (horizontal acceleration) | m/s2 | 2 |
3. Model and Definition

No. | Description | Unit | Interval name | ||||
D | C | F | V | ||||
1 | Rated voltage | kV | 12/24 | ||||
2 | Type of arc extinguishing chamber | / | SF6 | SF6 | Vacuum | ||
3 | Rated frequency | Hz | 50/60 | ||||
4 | Rated current | A | 630 | 630 | 125 | 630/1250 | |
5 | Temperature rise test current | A | 1.1Ir | ||||
6 | Rated power frequency 1min withstand voltage (phase to ground) | kV | 42/65 | ||||
7 | Peak value of rated lightning impulse withstand voltage (1.2/50μs, phase to ground) | kV | 75/145 | ||||
8 | Rated short-circuit breaking current | kA | / | / | 31.5 | 20/25 | |
9 | Rated short circuit making current | kA | / | / | 50/63 | 50/63 | |
10 | Rated short-term withstand current and duration | kA/s | 20/25/4 | 20/25/4 | / | 20/25/4 | |
11 | Rated peak withstand current | kA | 50/63 | 50/63 | / | 50/63 | |
12 | Arc duration | s | ≥1 | ||||
13 | Interruption times under rated active load | Times | / | 100 | 100 | 100 | |
14 | Short-time power frequency withstand voltage of auxiliary and control loops | kV | 2 | ||||
15 | Power supply | Control loop | V | DC24/DC48/DC110/AC220/DC220 | |||
Auxiliary circuit | V | DC24/DC48/DC110/AC220/DC220 | |||||
16 | Service life | Year | ≥30 | ||||
17 | Protection class | Cabinet shell | IP4X/IP3X | ||||
Compartment room | IP2X | ||||||
18 | Rated gas pressure (20ºC gauge pressure) | bar | 1.4 | ||||
19 | Annual gas leakage rate | V/V | 0.1% | ||||
20 | Partial discharge quantity | pC | Whole cabinet (1.1Ur) ≤ 20pC Single insulator (1.1Ur) ≤ 5pC |