GDBR-P
Universal Testing Machine
Electronic Load
Dynamic Load
Digital
Computer Control
12kg
AC220V
0 ~ 100A, auto switching range;
0 ~ 600V, auto switching range;
45Hz ~ 65Hz;
400*300*220mm
HV Hipot
Wooden Case
ISO, SGS
Wuhan China
9030899090
Product Description
GDBR-P Transformer Capacity and Load no load loss Tester
General Information
GDBR-P is mainly used to test capacity, No-load current, No-load loss, short circuit(load) loss, impedance voltage for transformers.
Features
Specifications
Environment condition
Measurement range
Voltage measurement: 0-10V
50kVA-31500kVA (for 35kV oil transformers)
50kVA-2500kVA (for 20kV dry transformers)
50kVA-2000kVA (for 35kV dry transformers)
Current: 0-100A, automatic switching range
Frequency: 45-65Hz.
Testing Accuracy
Insulation strength









General Information
GDBR-P is mainly used to test capacity, No-load current, No-load loss, short circuit(load) loss, impedance voltage for transformers.
Features
- Measure the capacity of various distribution transformers, which is convenient and accurate.
- Measure transformer No-load current, No-load loss, short circuit voltage and short circuit(load) loss.
- Automatic range switching is carried out inside the instrument, which allows a wide range of voltage and current measurements and simple wiring.
- When making three phase transformer No-load and load test, the instrument can automatically judge whether the wiring is correct or not, and display the vector diagram of three-phase voltage and current.
- Finish load test under 1000kVA below distribution transformer full current for single machine. Finish 3150kVA below distribution transformer load test under 1/3 rated current (Under 1/3 rated current, the instrument can be converted to load loss parameters under rated current.)
- All test results are corrected automatically. The instrument automatic correction as follows, waveform correction, temperature correction, non-rated voltage correction and non-rated current correction. The test results are more accurate.
- 320*240 high brightness LCD screen, with brightness adjustment. Touch buttons make the operation more convenient.
- The instrument can preset 40 sets parameters of test objects by users, and these parameters can be deleted and increased at any time according to need, so it is very convenient to use.
- Real-time clock, recording test date automatically, suitable for storage and management of test results.
- Built-in panel-type thermal printer, fast print test results.
- Power down store and browse data (test object settings, measurement results, test time) functions. Store up to 500 groups test results.
- Allows extended range measurement for external voltage transformer and current transformer. Measure test object of any parameters.
Specifications
Environment condition
- Temperature: -5ºC-40ºC
- Relative humidity: <95% (at 25ºC)
- Altitude: <2500m
- No vibration, no ultra-strong electromagnetic field
- Power input: AC220V± 10%, 45-55Hz.
Measurement range
- Internal source:
Voltage measurement: 0-10V
- Capacity test:
50kVA-31500kVA (for 35kV oil transformers)
50kVA-2500kVA (for 20kV dry transformers)
50kVA-2000kVA (for 35kV dry transformers)
- Measurement range of No-load and load test(need external voltage regulator, prepared by customer)
Current: 0-100A, automatic switching range
Frequency: 45-65Hz.
Testing Accuracy
- Voltage: ±0.2%FS at 2-100V; ±0.2% at 100-600V
- Current: ±0.2%FS at 0.5-10A; ±0.2% at 10-100A
- Power: ±0.5% at cosφ>0.1; ±1.0% at 0.02<cosφ<0.1
Insulation strength
- Insulation resistance of Voltage and current input terminal to shell ≥100MOhm
- Withstand voltage between power supply and shell is 2kV RMS, 1mins.
- Dimension: 400*300*220mm
- Weight: 6kg. (accessories are not included.)