hmjbc 1200
Life Time Support
1 Year or Extended
Protection Relay Test Set
0.5
Digital
Computer Control
49kgs
AC220V
0.1ms - 9999s
<0.1ms
70va / 140va
1-20
20-1000Hz
0.5 Degree
Production Relay Tester
-10°c~ 50°c
CE,ISO
Factory Report or The Third Party Report
Relay Tester
Hmjbc-702
30A Per Phase
10A Per Phase
120V AC Per Phase
HMDQ
Wooden Box with Foam Inside
customize
Hubei, China(Mainland)
9030820000
Product Description
6 phase Relay Protection Tester price
I. Brief introduction
Secondary current injection test set not only used for test all traditional relays and protection devices, but can also carry on all kinds for modern various microcomputer protection, especially for transformer differential protection and automatic transfer switch equipment.
II. Parameter
Type | |
Total Current channels | Six phases |
Total Voltage channels | Six phases |
AC Output current | 30A per phase or 180A (six phase parallel) |
DC Output current | 10A DC per phase |
AC output voltage | 120V AC per phase |
DC output voltage | 160V DC per phase |
III.Detail photos

Main parameter:
AC current output
Output current per phase under 6-phase output: 0~30A output precision 0.1 grade
Output current per phase under 3-phase output: 0~60A
Output current when 6-phase in parallel : 0~180A
Allowed phase current for long time working: 10A
The maximum output power of phase current 450VA
The maximum output power when 6-phase in parallel: 1000VA
The allowed working time when 6-phase in parallel: 10s
Frequency range(fundamental wave): 0~1000Hz
Harmonic times: 0~20
DC current output
Current output: 0~±10A / phase output precision 0.2 grade
The maximum output load voltage: 20V
AC voltage output
Phase voltage output: 0~120V output precision 0.1 grade
Line voltage output: 0~240V
Output power of phase voltage/ line voltage : 80VA / 100VA
Frequency range(fundamental wave): 0~1000Hz
Harmonic times: 0~20
DC voltage output
Phase voltage output: 0~±160V output precision 0.2 grade
Line voltage output: 0~±320V
The output power of phase voltage/ line voltage 70VA / 140VA
Input and output
8 channels input
Idle contact : 1~20mA,24V
Electric potential contacts: "0":0 ~ +6V; "1":+11 V ~ +250 V
4 pairs switch output: DC:220 V/0.2 A;AC:220 V/0.5 A
Time measurement range
0.1ms ~ 9999s , measurement accuracy <0.1ms
IV.Factory Release test

V.Application case



VI.Company profile
Wuhan Goldhome Hipot Electrical Co.,ltd is an ISO certified factory specially in manufacture electric test equipment with more than 20 years experience , located in Wuhan city , China .
Main products included PD free test set, AC/DC hipot tester, transformer tester, CT/PT analyzer , Circuit breaker tester, relay test set, transformer oil tester ,etc .
Warmly welcome to visit Goldhome Hipot factory !