High/Medium Voltage Vacuum Circuit Breaker Mv Vcb Gas Insulated Vacuum Circuit Breaker

Price $7500.00 Compare
Min Order 1 Piece
Shipping From Zhejiang, China
Popularity 492 people viewed
Quantity
+-
 

ROOQ ELECTRIC GROUP CO., LTD.

VIP   Audited Supplier 5 years
Profile Certified by SGS/BV
High Voltage Circuit Breakers
Electric Type
Normal Type Circuit Breaker
Vacuum
Fixed/Drawable
Vcb
3
Circuit Breaker
Conventional Circuit Breaker, Overcurrent Protection
ISO9001-2000, CE, CCC, ISO45001:2018/ISO14001:2015
ROOQ/Neutral/OEM
Wooden Case
IEC, GB, CE
China
Product Description
VS1 Indoor Vacuum Breaker 

Product Description


VS1 indoor medium voltage Vacuum Circuit Breaker is a three-phase AC 50Hz ,rated voltage 6KV,12KV,24KV switch equipment of power system.

Breaker adopts the integral design of the actuating mechanism and the breaker body, which can be used as a fixed installation unit or as an individual VCB carriage together with handcart. They have a long life expectancy. There is no adverse effect on the vacuum, even from frequent switching of operating and short-circuit currents.


Advantages

VS1 type VCB consist of operating mechanism and arc-extinguish chambers in front-back arrangement, its main conductive circuit is floor model structure. The vacuum arc-extinguish chamber is fixed in a vertical cannular insulation column made of epoxy resin by APG technology, therefore with high anti-creepage function. Such structure design greatly reduces the accumulation of dusts on the surface of vacuum arc- extinguish chamber, it not only can prevent the vacuum extinguish chamber from outside influences, but also can ensure to present high resistance state against the voltage effect even in warm-wet climate or heavy pollution environment.

1 - with reliable interlock functions, suitable for frequent operation
2 - low noise and energy consumed
3 - simple and robust construction.
4 - high operating reliability
5 - mechanical durability of switch : 20000 times, etc
 
Fields of application

1 - Transformers and distribution substations
2 - Generator control and protection
3 - Capacitor bank control and protection, etc

Mechanical parameters
No.ItemUnitDate
1Rated voltageKV1224
2Clearance between open contacts  mm11±113±1
3Over travel of moving contact3.5±0.53.5±0.5
4Three poles asynchronous time at openingms≤2≤2
5Moving contact bounce time at closingms≤2≤2
6Average opening speed  m/s0.9-1.20.9-1.2
7Average closing speed0.6-0.80.6-0.8
8Connecting pressure of close contacts   N20kA25kA31.5kA40kA20kA25kA31.5kA40kA
2000±2002400±2003100±2004250±2002000±2002400±2003100±2004750±200

Main characteristics
No.ItemUnit 
1Rated voltageKV1224
2Power frequency withstand voltage4265
3Lightning impulse voltage(peak value)75125
4FrequencyHz5050
5Rated current A630
1250
630 1250  1600 2000 2500 31501250 1600 2000 2500 3150 4000630
1250
630 1250 1600 2000 1600 200 2500
6Short circuit breaking currentkA20/2531.5402525/31.531.5/40
7Thermal stability currentkA20/2531.5402525/31.531.540
8Dynamic stable currentkA50/63801006380100
9short-circuit making current kA50/63801006380100
10Rated current breaking timeTimes2000020000
11Short circuit breaking current  timesTimes5030
12Operation voltageVAC/DC 110/220AC/DC 110/220
13Input powerW7070
14Storage time s1515
153 phase non-synchronousms22