SDC type SF6 fully insulated compact switchgear assembles the functional units in SF6 closed stainless steel chamber without any live parts exposed. It has the advantages of full insulation, full sealing, compact structure and convenient installation and operation. It is suitable for indoor and outdoor Installation, from the external environment, with high resistance to harsh environmental performance.
10kv Technical Specification | C Module | F Module | V Module | CB Module | ||
Load break switch | Switch fuse | Vacuum circuit breaker | Isolate/ earthing switch | Vacuum circuit breaker | Isolate/ earthing switch | |
Rated voltage | 12 | 12 | 24 | 24 | 24 | 24 |
Power frequence withstand voltage KV | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 |
Impulse withstand voltage KV | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
Rated current A | 630 | 125 | 630/1250 | 630/1250 | ||
Closed loop A | 630 | |||||
Off load cable charging A | 10 | |||||
Rated active load drop-oput current A | 630 | 630 | ||||
Earth fault breaking current A | 30 | 25 | ||||
When earth fault frop-out current of cable charging A | 17.4 | |||||
Short circuit drop-out current KA | 31.5 | 25 | ||||
Making capacity KA | 50 | note | 63 | 63 | 63 | 63 |
Short time current 4s KA | 20 | 20 | 25 | 20/25 | 20/25 | 20/25 |
Transfer current A | 1750 | |||||
Mechanical life times | 5000 | 5000 | 10000 | 3000 | 10000 | 3000 |
24kv Technical Specification | C Module | F Module | V Module | CB Module | ||
Load break switch | Switch fuse | Vacuum circuit breaker | Isolate/ earthing switch | Vacuum circuit breaker | Isolate/ earthing switch | |
Rated voltage | 24 | 24 | 24 | 24 | 24 | 24 |
Power frequence withstand voltage KV | 65/79 | 65/79 | 65/79 | 65/79 | 65/79 | 65/79 |
Impulse withstand voltage KV | 125/145 | 125/145 | 125/145 | 125/145 | 125/145 | 125/145 |
Rated current A | 630 | 125 | 630 | |||
Closed loop A | 630 | |||||
Off load cable charging A | 10 | |||||
Rated active load drop-oput current A | 31.5 | 630 | ||||
Earth fault breaking current A | 63 | |||||
When earth fault frop-out current of cable charging A | 43.3 | |||||
Short circuit drop-out current KA | 20 note | 20 | 20 | 25 | ||
Making capacity KA | 50 | 50 note | 50 | 50 | 63 | 63 |
Short time current 4s KA | 20 | 20 | 20 | 25 | 25 | |
Transfer current A | 1400 | |||||