LD47-125PV
Low Voltage Circuit Breakers
Electric Type
Normal Type Circuit Breaker
Air
DIN Rail
MCB
Circuit Breaker
CE
63A 80A 100A 125A
12V, 24V, 48V, 250V, 500V, 750V, 1000V
10ka
50/60Hz
Thermal - Magnetic
C
WZAZURE /OEM
Conventional Export Packaging
80pcs/ctn
Zhejiang, China
8536200000
Product Description
125A DC Breaker 2P 4P 500VDC 1000VDC DC MCB 125A Circuit Breaker for Solar System
LWD47-125PV high breaking capacity circuit breaker is specially for solar pv system . the current is from 63A to 125A and voltage up to 1000VDC .It is mainly used for the overloading and short circuit protection in DC distribution system Equipment and electric equipment. It can be widely used in electric, post, traffic, mining enterprise and different kinds of fields. according IEC60947-2 standard.






LWD47-125PV high breaking capacity circuit breaker is specially for solar pv system . the current is from 63A to 125A and voltage up to 1000VDC .It is mainly used for the overloading and short circuit protection in DC distribution system Equipment and electric equipment. It can be widely used in electric, post, traffic, mining enterprise and different kinds of fields. according IEC60947-2 standard.
Technical parameters
Molel Type | LD47-125PV | ||||||||
Frame Degree Rated Current | 125A | ||||||||
Pole | 1P, 2P, 3P, 4P | ||||||||
Rated Operating Voltage (VDC) | 12V, 24V, 48V, 250V, 500V, 750V, 1000V | ||||||||
Rated Current In (A) | 63A ,80A, 100A, 125A | ||||||||
Rated Insulation Voltage Ui (VDC) | 1200VDC | ||||||||
Rated Impact Voltage Uimp (kV) | 4 | ||||||||
Ultimate Breaking Capacity Icu (kA) | 6 | ||||||||
Run Breaking Capacity Ics (%Icu) | 0.75 | ||||||||
Curve Type | C | ||||||||
Trip Type | Thermal - Magnetic | ||||||||
Mechanical | Actual average value | 20000 times | |||||||
Standard value | 8500 times | ||||||||
Eletric | Actual average value | 2500 times | |||||||
Standard value | 1500 times | ||||||||
Wiring Capacity | In≤ 32A, 1~25mm²; In≥ 40A, 10~35mm² | ||||||||
Ambient Temperature | -20ºC ~ +70ºC | ||||||||
Altitude | ≤ 2000m | ||||||||
Pollution Level | 3 | ||||||||
Installation Environment | No obvious shock and vibration | ||||||||
Installation Category | Class III | ||||||||
Installation | Standard din rail | ||||||||
Weight (KG) | 0.18 | 0.36 | 0.54 | 0.72 | |||||
Dimensions (mm) | W | 27 | 54 | 81 | 108 | ||||
H | 80 | 80 | 80 | 80 | |||||
D | 71 | 71 | 71 | 71 |
Product Display






FAQ :
Q1: Can I print my logo on the products?
A: Yes, OEM available. ( MOQ : 200 Pieces )
Q2: Do you have inspection procedures for products?
A: Our products100% self-inspection and testing before packing.
Q3: How about delivery time of the order?
A: 5-7 working days after getting deposit. ( We have stock )
Any requirements or question,welcome to "Send" us an e-mail Now!!!