Structure
Conductor : Plain annealed copper solid or stranded (class 1 or 2) conductor complying with IEC 60228Insulation : 90°C cross linked XLPE insulation complying with IEC 60502-1
Interlining: PVC type ST2 to IEC 60502, black
Armoring: STA(Steel-Tape Armoring)
Sheath : PVC type ST2 to IEC 60502, black
Detailed Product Description
Conductor:Class 2Insulation:XLPE
Sheath: PVC
Cable Speciification: Fire Resistant
Marking: Embossing Or Printing
Sheath Color: Black Or Red
Standards:
International: IEC 60502, IEC 60228, IEC 60332, IEC 60754China: GB/T 12706.1-2008, GB/T 19666-2005
Other standards such as BS,VDE and ICEA upon request
Applications
Laying in room ,tunnel ,cable trench ,and pipes.Technical data
Rated voltage: 0.6/1kV
Maximum Conductor Temperature: under normal (90°C), emergency (130°C) or short circuit no more than 5 s (250°C) conditions.
Min. Ambient Temp. 0°C, after installation and only when cable is in a fixed position
Min. Bending Radius: 20 x cable O.D for single-core non-armoured cables
15 x cable O.D for single-core armoured cables
15 x cable O.D for multi-core non-armoured cables
12 x cable O.D for multi-core armoured cables

Nom. Cross-section of Conductor mm2 | Strands No./Dia. Of Conductor | Insulation Thickness mm | Steel Tape Thickness mm | Sheath Thickness mm | Approx. O.D. mm | Approx. Weight kg/km | Max. D.C Resistance of Conductor (20 ºC) | Testing Voltage A.C | Current Rating | |
In air (A) | In soil(A) | |||||||||
1×10 | 7/1.33 | 0.7 | 0.2 | 1.8 | 11.8 | 265 | 1.83 | 3.5 | 77 | 94 |
1×16 | 7/1.67 | 0.7 | 0.2 | 1.8 | 12.8 | 338 | 1.15 | 3.5 | 100 | 120 |
1×25 | 7/2.10 | 0.9 | 0.2 | 1.8 | 14.5 | 458 | 0.727 | 3.5 | 130 | 155 |
1×35 | 7/2.48 | 0.9 | 0.2 | 1.8 | 15.6 | 571 | 0.524 | 3.5 | 160 | 185 |
1×50 | 10/2.56 | 1 | 0.2 | 1.8 | 16.8 | 712 | 0.387 | 3.5 | 195 | 220 |
1×70 | 14/2.56 | 1.1 | 0.2 | 1.8 | 18.7 | 940 | 0.268 | 3.5 | 245 | 270 |
1×95 | 19/2.56 | 1.1 | 0.2 | 1.8 | 20.3 | 1209 | 0.193 | 3.5 | 300 | 320 |
1×120 | 24/2.56 | 1.2 | 0.2 | 1.8 | 22 | 1465 | 0.153 | 3.5 | 349 | 365 |
1×150 | 30/2.56 | 1.4 | 0.2 | 1.8 | 23.8 | 1757 | 0.124 | 3.5 | 400 | 410 |
1×185 | 37/2.56 | 1.6 | 0.2 | 1.8 | 25.9 | 2157 | 0.0991 | 3.5 | 465 | 465 |
1×240 | 48/2.58 | 1.7 | 0.2 | 1.8 | 28.3 | 2732 | 0.0754 | 3.5 | 550 | 540 |
1×300 | 60/2.58 | 1.8 | 0.2 | 1.9 | 30.9 | 3344 | 0.0601 | 3.5 | 635 | 610 |
1×400 | 60/2.93 | 2 | 0.2 | 2 | 34.4 | 4260 | 0.047 | 3.5 | 745 | 695 |
1×500 | 60/3.33 | 2.2 | 0.5 | 2.2 | 39.6 | 5673 | 0.0366 | 3.5 | 860 | 780 |
1×630 | 60/3.76 | 2.4 | 0.5 | 2.3 | 44 | 7133 | 0.0283 | 3.5 | 990 | 880 |
Nom. Cross-section of Conductor mm2 | Strands No./Dia. Of Conductor | Insulation Thickness mm | Steel Tape Thickness mm | Sheath Thickness mm | Approx. O.D. mm | Approx. Weight kg/km | Max. D.C Resistance of Conductor (20 ºC) | Testing Voltage A.C | Current Rating | |
In air (A) | In soil(A) | |||||||||
2×1.5 | 1/1.38 | 0.7 | 0.2 | 1.8 | 12.3 | 230 | 12.1 | 3.5 | 20 | 31 |
2×2.5 | 1/1.76 | 0.7 | 0.2 | 1.8 | 13.1 | 266 | 7.56 | 3.5 | 27 | 41 |
2×4 | 1/2.23 | 0.7 | 0.2 | 1.8 | 14 | 316 | 4.61 | 3.5 | 35 | 53 |
2×6 | 1/2.74 | 0.7 | 0.2 | 1.8 | 15 | 378 | 3.08 | 3.5 | 45 | 66 |
2×10 | 7/1.33 | 0.7 | 0.2 | 1.8 | 17.5 | 516 | 1.83 | 3.5 | 63 | 90 |
2×16 | 7/1.67 | 0.7 | 0.2 | 1.8 | 19.5 | 672 | 1.15 | 3.5 | 84 | 117 |
2×25 | 7/2.10 | 0.9 | 0.2 | 1.8 | 22.9 | 937 | 0.727 | 3.5 | 113 | 151 |
2×35 | 7/2.48 | 0.9 | 0.2 | 1.8 | 25.2 | 1181 | 0.524 | 3.5 | 139 | 181 |
2×50 | 10/2.56 | 1 | 0.2 | 1.8 | 21.8 | 1281 | 0.387 | 3.5 | 161 | 210 |
2×70 | 14/2.56 | 1.1 | 0.2 | 1.9 | 24.8 | 1734 | 0.268 | 3.5 | 204 | 257 |
2×95 | 19/2.56 | 1.1 | 0.2 | 2 | 27.5 | 2278 | 0.193 | 3.5 | 252 | 310 |
2×120 | 24/2.56 | 1.2 | 0.5 | 2.2 | 31.3 | 3095 | 0.153 | 3.5 | 291 | 351 |
2×150 | 30/2.56 | 1.4 | 0.5 | 2.3 | 34.5 | 3730 | 0.124 | 3.5 | 333 | 393 |
2×185 | 37/2.56 | 1.6 | 0.5 | 2.5 | 38.2 | 4618 | 0.0991 | 3.5 | 385 | 445 |
2×240 | 48/2.56 | 1.7 | 0.5 | 2.6 | 42.2 | 5832 | 0.0754 | 3.5 | 457 | 516 |
2×300 | 60/2.56 | 1.8 | 0.5 | 2.8 | 46.3 | 7142 | 0.0601 | 3.5 | 527 | 583 |
Nom. Cross-section of Conductor mm2 | Strands No./Dia. Of Conductor | Insulation Thickness mm | Steel Tape Thickness mm | Sheath Thickness mm | Approx. O.D. mm | Approx. Weight kg/km | Max. D.C Resistance of Conductor (20 ºC) | Testing Voltage A.C | Current Rating | |
In air (A) | In soil(A) | |||||||||
3×1.5 | 1/1.38 | 0.7 | 0.2 | 1.8 | 12.7 | 256 | 12.1 | 3.5 | 20 | 31 |
3×2.5 | 1/1.76 | 0.7 | 0.2 | 1.8 | 13.5 | 302 | 7.56 | 3.5 | 27 | 41 |
3×4 | 1/2.23 | 0.7 | 0.2 | 1.8 | 14.6 | 367 | 4.61 | 3.5 | 35 | 53 |
3×6 | 1/2.74 | 0.7 | 0.2 | 1.8 | 15.7 | 449 | 3.08 | 3.5 | 45 | 66 |
3×10 | 7/1.33 | 0.7 | 0.2 | 1.8 | 18.4 | 627 | 1.83 | 3.5 | 63 | 90 |
3×16 | 7/1.67 | 0.7 | 0.2 | 1.8 | 20.5 | 838 | 1.15 | 3.5 | 84 | 117 |
3×25 | 7/2.10 | 0.9 | 0.2 | 1.8 | 24.2 | 1191 | 0.727 | 3.5 | 113 | 151 |
3×35 | 7/2.48 | 0.9 | 0.2 | 1.8 | 26.6 | 1528 | 0.524 | 3.5 | 139 | 181 |
3×50 | 10/2.56 | 1 | 0.2 | 1.9 | 25.5 | 1814 | 0.387 | 3.5 | 161 | 210 |
3×70 | 14/2.56 | 1.1 | 0.2 | 2 | 29 | 2474 | 0.268 | 3.5 | 204 | 257 |
3×95 | 19/2.56 | 1.1 | 0.5 | 2.1 | 33.5 | 3598 | 0.193 | 3.5 | 252 | 310 |
3×120 | 24/2.56 | 1.2 | 0.5 | 2.3 | 36.7 | 4386 | 0.153 | 3.5 | 291 | 351 |
3×150 | 30/2.56 | 1.4 | 0.5 | 2.4 | 40.7 | 5332 | 0.124 | 3.5 | 333 | 393 |
3×185 | 37/2.56 | 1.6 | 0.5 | 2.5 | 44.6 | 6562 | 0.0991 | 3.5 | 385 | 445 |
3×240 | 48/2.56 | 1.7 | 0.5 | 2.8 | 50.2 | 8414 | 0.0754 | 3.5 | 457 | 516 |
3×300 | 60/2.56 | 1.8 | 0.5 | 2.9 | 54.9 | 10306 | 0.0601 | 3.5 | 527 | 583 |
Nom. Cross-section of Conductor mm2 | Strands No./Dia. Of Conductor | Insulation Thickness mm | Steel Tape Thickness mm | Sheath Thickness mm | Approx. O.D. mm | Approx. Weight kg/km | Max. D.C Resistance of Conductor (20 ºC) | Testing Voltage A.C | Current Rating | |
In air (A) | In soil(A) | |||||||||
4×1.5 | 1/1.38 | 0.7 | 0.2 | 1.8 | 13.5 | 291 | 12.1 | 3.5 | 20 | 31 |
4×2.5 | 1/1.76 | 0.7 | 0.2 | 1.8 | 14.4 | 348 | 7.56 | 3.5 | 27 | 41 |
4×4 | 1/2.23 | 0.7 | 0.2 | 1.8 | 15.5 | 430 | 4.61 | 3.5 | 35 | 53 |
4×6 | 1/2.74 | 0.7 | 0.2 | 1.8 | 16.7 | 534 | 3.08 | 3.5 | 45 | 66 |
4×10 | 7/1.33 | 0.7 | 0.2 | 1.8 | 19.8 | 758 | 1.83 | 3.5 | 63 | 90 |
4×16 | 7/1.67 | 0.7 | 0.2 | 1.8 | 22.2 | 1027 | 1.15 | 3.5 | 84 | 117 |
4×25 | 7/2.10 | 0.9 | 0.2 | 1.8 | 26.3 | 1479 | 0.727 | 3.5 | 113 | 151 |
4×35 | 7/2.48 | 0.9 | 0.2 | 1.8 | 29.1 | 1914 | 0.524 | 3.5 | 139 | 181 |
4×50 | 10/2.56 | 1 | 0.2 | 2 | 28.4 | 2334 | 0.387 | 3.5 | 161 | 210 |
4×70 | 14/2.56 | 1.1 | 0.5 | 2.1 | 33.6 | 3518 | 0.268 | 3.5 | 204 | 257 |
4×95 | 19/2.56 | 1.1 | 0.5 | 2.3 | 37.9 | 4638 | 0.193 | 3.5 | 252 | 310 |
4×120 | 24/2.56 | 1.2 | 0.5 | 2.4 | 41.8 | 5701 | 0.153 | 3.5 | 291 | 351 |
4×150 | 30/2.56 | 1.4 | 0.5 | 2.6 | 46 | 6912 | 0.124 | 3.5 | 333 | 393 |
4×185 | 37/2.56 | 1.6 | 0.5 | 2.7 | 51 | 8562 | 0.0991 | 3.5 | 385 | 445 |
4×240 | 48/2.56 | 1.7 | 0.5 | 3 | 57.7 | 11052 | 0.0754 | 3.5 | 457 | 516 |
4×300 | 60/2.56 | 1.8 | 0.5 | 3.1 | 62.7 | 13479 | 0.0601 | 3.5 | 527 | 583 |
Nom. Cross-section of Conductor mm2 | Strands No./Dia. Of Conductor | Insulation Thickness mm | Steel Tape Thickness mm | Sheath Thickness mm | Approx. O.D. mm | Approx. Weight kg/km | Max. D.C Resistance of Conductor (20 ºC) | Testing Voltage A.C | Current Rating | |
In air (A) | In soil(A) | |||||||||
5×1.5 | 1/1.38 | 0.7 | 0.2 | 1.8 | 14.3 | 328 | 12.1 | 3.5 | 20 | 31 |
5×2.5 | 1/1.76 | 0.7 | 0.2 | 1.8 | 15.3 | 397 | 7.56 | 3.5 | 27 | 41 |
5×4 | 1/2.23 | 0.7 | 0.2 | 1.8 | 16.6 | 497 | 4.61 | 3.5 | 35 | 53 |
5×6 | 1/2.74 | 0.7 | 0.2 | 1.8 | 18 | 623 | 3.08 | 3.5 | 45 | 66 |
5×10 | 7/1.33 | 0.7 | 0.2 | 1.8 | 21.4 | 895 | 1.83 | 3.5 | 63 | 90 |
5×16 | 7/1.67 | 0.7 | 0.2 | 1.8 | 24.1 | 1225 | 1.15 | 3.5 | 84 | 117 |
5×25 | 7/2.10 | 0.9 | 0.2 | 1.8 | 28.7 | 1780 | 0.727 | 3.5 | 113 | 151 |
5×35 | 7/2.48 | 0.9 | 0.2 | 1.9 | 31.9 | 2329 | 0.524 | 3.5 | 139 | 181 |
5×50 | 19/1.86 | 1 | 0.2 | 2.1 | 31.9 | 2879 | 0.387 | 3.5 | 161 | 210 |
5×70 | 14/2.56 | 1.1 | 0.5 | 2.2 | 37.8 | 4327 | 0.268 | 3.5 | 204 | 257 |
5×95 | 19/2.56 | 1.1 | 0.5 | 2.4 | 42.8 | 5740 | 0.193 | 3.5 | 252 | 310 |
5×120 | 24/2.56 | 1.2 | 0.5 | 2.5 | 46.8 | 7027 | 0.153 | 3.5 | 291 | 351 |
5×150 | 30/2.56 | 1.4 | 0.5 | 2.7 | 52.1 | 8591 | 0.124 | 3.5 | 333 | 393 |
5×185 | 37/2.56 | 1.6 | 0.5 | 2.9 | 57.5 | 10636 | 0.0991 | 3.5 | 385 | 445 |
5×240 | 48/2.56 | 1.7 | 0.5 | 3.2 | 64.5 | 13651 | 0.0754 | 3.5 | 457 | 516 |
5×300 | 60/2.56 | 1.8 | 0.5 | 3.4 | 71 | 16764 | 0.0601 | 3.5 | 527 | 583 |
Nom. Cross-section of Conductor mm2 | Strands No./Dia. Of Conductor | Insulation Thickness mm | Steel Tape Thickness mm | Sheath Thickness mm | Approx. O.D. mm | Approx. Weight kg/km | Max. D.C Resistance of Conductor (20 ºC) | Testing Voltage A.C | Current Rating | |
In air (A) | In soil(A) | |||||||||
3×2.5+1×1.5 | 1/1.76 | 0.7 | 0.2 | 1.8 | 14.1 | 334 | 7.56 | 3.5 | 27 | 41 |
3×4+1×2.5 | 1/2.23 | 0.7 | 0.2 | 1.8 | 15.2 | 410 | 4.61 | 3.5 | 35 | 53 |
3×6+1×4 | 1/2.74 | 0.7 | 0.2 | 1.8 | 16.4 | 508 | 3.08 | 3.5 | 45 | 66 |
3×10+1×6 | 7/1.33 | 0.7 | 0.2 | 1.8 | 19 | 701 | 1.83 | 3.5 | 63 | 90 |
3×16+1×10 | 7/1.67 | 0.7 | 0.2 | 1.8 | 21.6 | 959 | 1.15 | 3.5 | 84 | 117 |
3×25+1×16 | 7/2.10 | 0.9 | 0.2 | 1.8 | 25.3 | 1365 | 0.727 | 3.5 | 113 | 151 |
3×35+1×16 | 7/2.48 | 0.9 | 0.2 | 1.8 | 27.4 | 1689 | 0.524 | 3.5 | 139 | 181 |
3×50+1×25 | 10/2.56 | 1 | 0.2 | 1.9 | 27.9 | 2115 | 0.387 | 3.5 | 161 | 210 |
3×70+1×35 | 14/2.56 | 1.1 | 0.2 | 2 | 32.1 | 2896 | 0.268 | 3.5 | 204 | 257 |
3×95+1×50 | 19/2.56 | 1.1 | 0.5 | 2.2 | 37.4 | 4213 | 0.193 | 3.5 | 252 | 310 |
3×120+1×70 | 24/2.56 | 1.2 | 0.5 | 2.3 | 41.4 | 5251 | 0.153 | 3.5 | 291 | 351 |
3×150+1×70 | 30/2.56 | 1.4 | 0.5 | 2.4 | 45 | 6175 | 0.124 | 3.5 | 333 | 393 |
3×185+1×95 | 37/2.56 | 1.6 | 0.5 | 2.6 | 50 | 7731 | 0.0991 | 3.5 | 385 | 445 |
3×240+1×120 | 48/2.56 | 1.7 | 0.5 | 2.8 | 56 | 9857 | 0.0754 | 3.5 | 457 | 516 |
3×300+1×150 | 60/2.56 | 1.8 | 0.5 | 3 | 61.3 | 12042 | 0.0601 | 3.5 | 527 | 583 |
3×2.5+2×1.5 | 1/1.76 | 0.7 | 0.2 | 1.8 | 14.9 | 369 | 7.56 | 3.5 | 27 | 41 |
3×4+2×2.5 | 1/2.23 | 0.7 | 0.2 | 1.8 | 16.1 | 457 | 4.61 | 3.5 | 35 | 53 |
3×6+2×4 | 1/2.74 | 0.7 | 0.2 | 1.8 | 17.4 | 573 | 3.08 | 3.5 | 45 | 66 |
3×10+2×6 | 7/1.33 | 0.7 | 0.2 | 1.8 | 20 | 785 | 1.83 | 3.5 | 63 | 90 |
3×16+2×10 | 7/1.67 | 0.7 | 0.2 | 1.8 | 23 | 1092 | 1.15 | 3.5 | 84 | 117 |
3×25+2×16 | 7/2.10 | 0.9 | 0.2 | 1.8 | 26.8 | 1556 | 0.727 | 3.5 | 113 | 151 |
3×35+2×16 | 7/2.48 | 0.9 | 0.2 | 1.8 | 28.7 | 1874 | 0.524 | 3.5 | 139 | 181 |
3×50+2×25 | 10/2.56 | 1 | 0.2 | 2 | 29.1 | 2384 | 0.387 | 3.5 | 161 | 210 |
3×70+2×35 | 14/2.56 | 1.1 | 0.5 | 2.1 | 34.4 | 3583 | 0.268 | 3.5 | 204 | 257 |
3×95+2×50 | 19/2.56 | 1.1 | 0.5 | 2.3 | 38.5 | 4692 | 0.193 | 3.5 | 252 | 310 |
3×120+2×70 | 24/2.56 | 1.2 | 0.5 | 2.4 | 42.5 | 5909 | 0.153 | 3.5 | 291 | 351 |
3×150+2×70 | 30/2.56 | 1.4 | 0.5 | 2.5 | 46.8 | 6889 | 0.124 | 3.5 | 333 | 393 |
3×185+2×95 | 37/2.56 | 1.6 | 0.5 | 2.7 | 52.5 | 8744 | 0.0991 | 3.5 | 385 | 445 |
3×240+2×120 | 48/2.56 | 1.7 | 0.5 | 2.9 | 58.5 | 11068 | 0.0754 | 3.5 | 457 | 516 |
3×300+2×150 | 60/2.56 | 1.8 | 0.5 | 3.1 | 64.5 | 13551 | 0.0601 | 3.5 | 527 | 583 |
Nom. Cross-section of Conductor mm2 | Strands No./Dia. Of Conductor | Insulation Thickness mm | Steel Tape Thickness mm | Sheath Thickness mm | Approx. O.D. mm | Approx. Weight kg/km | Max. D.C Resistance of Conductor (20 ºC) | Testing Voltage A.C | Current Rating | |
In air (A) | In soil(A) | |||||||||
4×2.5+1×1.5 | 1/1.76 | 0.7 | 0.2 | 1.8 | 15.1 | 383 | 7.56 | 3.5 | 27 | 41 |
4×4+1×2.5 | 1/2.23 | 0.7 | 0.2 | 1.8 | 16.4 | 477 | 4.61 | 3.5 | 35 | 53 |
4×6+1×4 | 1/2.74 | 0.7 | 0.2 | 1.8 | 17.7 | 598 | 3.08 | 3.5 | 45 | 66 |
4×10+1×6 | 7/1.33 | 0.7 | 0.2 | 1.8 | 20.7 | 839 | 1.83 | 3.5 | 63 | 90 |
4×16+1×10 | 7/1.67 | 0.7 | 0.2 | 1.8 | 23.5 | 1159 | 1.15 | 3.5 | 84 | 117 |
4×25+1×16 | 7/2.10 | 0.9 | 0.2 | 1.8 | 27.7 | 1667 | 0.727 | 3.5 | 113 | 151 |
4×35+1×16 | 7/2.48 | 0.9 | 0.2 | 1.9 | 30.4 | 2107 | 0.524 | 3.5 | 139 | 181 |
4×50+1×25 | 10/2.56 | 1 | 0.2 | 2 | 29.5 | 2590 | 0.387 | 3.5 | 161 | 210 |
4×70+1×35 | 14/2.56 | 1.1 | 0.5 | 2.2 | 35 | 3900 | 0.268 | 3.5 | 204 | 257 |
4×95+1×50 | 19/2.56 | 1.1 | 0.5 | 2.3 | 39.3 | 5144 | 0.193 | 3.5 | 252 | 310 |
4×120+1×70 | 24/2.56 | 1.2 | 0.5 | 2.5 | 43.2 | 6386 | 0.153 | 3.5 | 291 | 351 |
4×150+1×70 | 30/2.56 | 1.4 | 0.5 | 2.6 | 48.3 | 7683 | 0.124 | 3.5 | 333 | 393 |
4×185+1×95 | 37/2.56 | 1.6 | 0.5 | 2.8 | 53.2 | 9566 | 0.0991 | 3.5 | 385 | 445 |
4×240+1×120 | 48/2.56 | 1.7 | 0.5 | 3 | 59.7 | 12219 | 0.0754 | 3.5 | 457 | 516 |
4×300+1×150 | 60/2.56 | 1.8 | 0.5 | 3.3 | 65.6 | 14985 | 0.0601 | 3.5 | 527 | 583 |
Related Type
Type | Description | No. of cores | Nominal Cross Section of Conductor |
YJV22 | Copper conductor XLPE insulation Steel Tape Armoured PVC outer sheath Power Cable | 1, 2, 3, 4, 3+1, 5, 4+1, 3+2 | 1.5~630mm² |
YJV23 | Copper conductor XLPE insulation Steel Tape Armoured PE outer sheath Power Cable | 1, 2, 3, 4, 3+1, 5, 4+1, 3+2 | 1.5~630mm² |
ZA-YJV22 ZB-YJV22 ZC-YJV22 | Copper conductor XLPE insulation Steel Tape Armoured flame-retardant Power Cable | 1, 2, 3, 4, 3+1, 5, 4+1, 3+2 | 1.5~630mm² |
WDZA-YJY23 WDZB-YJY23 WDZC-YJY23 | Copper conductor XLPE insulation Steel Tape Armoured Low Smoke Halogen Free Or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable | 1, 2, 3, 4, 3+1, 5, 4+1, 3+2 | 1.5~630mm² |
NH-YJV22 | Copper conductor XLPE insulation Steel Tape Armoured fire-resistant Power Cable | 1, 2, 3, 4, 3+1, 5, 4+1, 3+2 | 1.5~630mm² |



How can I get some samples?
We provide free sample and will courier to you by DHL, FEDEX, UPS, TNT, etc. swiftly according to your requirements.
How do you control the quality?
QC department will control the quality during the full production process.
Inspector will inspect each item according to the order, inspection report will transfer to you before loading.
Any third party inspection will be accepted during the production or before loading, such as SGS, BV, etc.
After-sale dept will follow the order and pay high attention on the feedback from your side after all the products delivered. Any quality problem, we will arrange the technical personnel to solve and bear the corresponding customer losses..
What if the cable we need have some differences on specifications from yours?
Any differences, we can design and produce according to your requests.
What's the package of the goods?
Usually wooden or steel drum or coil, or according to your requirement
What's the lead time?
Usually 10-30 working days.
Welcome your inquiry and email soon......