LZCK-55
Instrument
Current Transformer
Single
Outdoor
Protection, Measurement
Single Layer & Tightly Wound Type
Epoxy Resin
Active Type
Combined Type
Electromagnetic Type
100A Split Core Current Transformer Outdoor
100A
5A
2.5va
Orange
Current Measurement(Energy Meter)
2.5m(Standard)
IEC60044-1, IEC61869
2kg
IP67
GFUVE
Standard Export Carton Packaging
LZCK-55 100/5A 0.5S
Beijing, China
854010000
Product Description
LZCK-55 IP67 epoxy resin outdoor 100A split core current transformer 5A
LZCK series outdoor waterproof current transformers are applicable for AC power system 35kV and measurement of current of power supply equipment below 10KV also can be used for microcomputer protection. This type of current transformer employs imported silicon steel which with high permeability as magnetic material, has the characteristics of Small magnetic circuit loss and can be split, its semicircular core and secondary windings employ high quality epoxy resin vacuum, casting in plastic-case(ABS or PC) which is flame retardance anti-moisture, stable performance, no maintenance.



APPLICATIONS
Energy meter
Power meter
Power factor meter
Ammeter
Distribution transformer monitor
Power monitor

LZCK series outdoor waterproof current transformers are applicable for AC power system 35kV and measurement of current of power supply equipment below 10KV also can be used for microcomputer protection. This type of current transformer employs imported silicon steel which with high permeability as magnetic material, has the characteristics of Small magnetic circuit loss and can be split, its semicircular core and secondary windings employ high quality epoxy resin vacuum, casting in plastic-case(ABS or PC) which is flame retardance anti-moisture, stable performance, no maintenance.



APPLICATIONS
Energy meter
Power meter
Power factor meter
Ammeter
Distribution transformer monitor
Power monitor
PARAMETERS
Technical parameters | |
---|---|
Standards | IEC60044-1; IEC 61869-2; NTC 2205; GB1208-2006; ANSI C57.13 |
Accuracy Class | 0.5S, 0.5%, 1%, 3% |
Range of primary rated current | 100-1500A |
Range of Rated load | ≤10VA |
Rated frequency | 50/60Hz |
Rated secondary current | 5A or 1A |
Rated short-time thermal current | 40kA, 1S |
Rated continuous thermal current | 150%I1n |
Secondary winding power frequency withstand voltage | 3kV, 1min |
Safety Factor Rating | (FS) <10 |
Output signal | 1A, 5A, 333mV, 1V or 5V(customized) |
Cable length | 2.5m, 5m, 10m(customized) |
Flame retardant ABS plastic shell inside, jaw waterproof apron. | |
Mechanical parameters | |
Aperture (mm) | Φ55 |
Dimensions (W×D×H) (mm) | 180×138×52 |
Weight (kg) | 2 |
Working conditions | |
Operating temperature | -35°C to +65°C, not exceeding +40°C |
Storage temperature | -40°C to +70°C |
Ingress Protection | IP65 |
Environment | outdoors or indoors |
The Height of above sea level | 0- 3000m |
Conditions | No existence of severely begrimed, erosive and radioactive gas in the air. Continuous working under the rated current is allowed. |
SELECTION GUIDE
Model | Primary rated current | Rated load | Aperture (mm) | Description (mm) | Weight (kg) | Material | Water-proof |
---|---|---|---|---|---|---|---|
LZCK-55 | 100-1500A | ≤10VA | φ55 | 180×138×52 | 2 | PC | IP65 |
LMCK185-10 | 300-3000A | ≤25VA | φ185 | 350×283×55 | 4.5 | PC | IP65 |
LZCK310-10 | 300-600A | ≤10VA | φ50 | φ50 x φ110 x 32 | 1 | Resin | silicon case (option) |
LZCK322-10 | 30-600A | ≤10VA | φ50 | φ50 x φ110 x 52 | 1.6 | Resin | silicon case (option) |
LZCK350-10 | 20-600A | ≤25VA | φ50 | φ50 x φ110 x 105 | 3.1 | Resin | silicon case (option) |
LZCG530-10 | 30-600A | ≤20VA | φ45 | φ45 x φ120 x 65 | 2.1 | Resin | silicon case (option) |
Photo