Construction, Underground, Industrial, Power Station
Low and Medium Voltage Cable
XLPE
PVC
Round Wire
Red Copper Wire
ISO, CCC, CE, VDE
Pallet or Drum
10-630mm2
China
8544492100
Product Description

Fixed laying in metallurgy, electric power, construction and other industries of indoor, cable trench, pipeline, direct buried and other requirements to withstand external mechanical occasions.
The source of raw materials for production is wide and the price is low, easy to process and manufacture.
The product uses crosslinked polyethylene insulation, compared with PVC insulated cable, good insulation performance, conductor operating temperature is higher, up to 90 degrees.
The product adopts steel wire armouring, which can withstand large mechanical tension.
The source of raw materials for production is wide and the price is low, easy to process and manufacture.
The product uses crosslinked polyethylene insulation, compared with PVC insulated cable, good insulation performance, conductor operating temperature is higher, up to 90 degrees.
The product adopts steel wire armouring, which can withstand large mechanical tension.
This product is suitable for AC 50Hz, rated voltage 0.6/1kV(system maximum voltage 1.2kV) power line transmission power.
Rated voltage
The rated power frequency AC voltage is 0.6/1kV, and the maximum voltage of the AC system should not exceed 1.2kV.
Operating temperature
The maximum allowable working temperature of the cable conductor for a long time is 90ºC. In the case of short circuit, the maximum temperature of the cable conductor shall not exceed 250 ° C and the duration shall not exceed 5s.
Ambient temperature
Minimum operating ambient temperature -15 ° C.
Laying temperature
The laying temperature of the cable should not be lower than 0ºC.
The rated power frequency AC voltage is 0.6/1kV, and the maximum voltage of the AC system should not exceed 1.2kV.
Operating temperature
The maximum allowable working temperature of the cable conductor for a long time is 90ºC. In the case of short circuit, the maximum temperature of the cable conductor shall not exceed 250 ° C and the duration shall not exceed 5s.
Ambient temperature
Minimum operating ambient temperature -15 ° C.
Laying temperature
The laying temperature of the cable should not be lower than 0ºC.

Size (mm2) | Outer Diameter of Conductor | Armor Specification | Reference Outside Diameter | Weight |
4*10 | 4.05 | 41*1.25 | 22.6 | 1123.3 |
4*25 | 6.42 | 45*1.6 | 30.0 | 2188.7 |
4*50 | 7.5*10.5 | 46*1.6 | 30.7 | 3001.8 |
4*95 | 11.0*13.3 | 50*2.0 | 40.6 | 5412.5 |
4*120 | 12.0*17.0 | 44*2.5 | 45.1 | 6952.2 |
4*300 | 19.5*27.9 | 67*2.5 | 66.0 | 15248.1 |