The KYN28-12 (GZS1) armored central AC metal-enclosed switchgear is designed for high-performance power distribution in three-phase AC 50Hz systems, with a rated voltage of 12kV. This switchgear is suitable for energy reception, distribution, control, and circuit protection, making it ideal for power stations, substations, and industrial facilities. It meets the requirements of GB3906, GB/T11022, and IEC60298 standards, ensuring reliable operation in demanding environments.
Features
- Robust and Versatile Design: The KYN28-12 is built with a metal armor structure and features modular components for flexible installation and maintenance. This design supports various operational configurations and facilitates seamless integration with high voltage power systems.
- Reliable Circuit Protection: Equipped with ZN63A-12 (VS1) or imported VD4 vacuum circuit breakers, the switchgear offers high short-circuit breaking capacity and stability, with options for manual or electric operation. The breakers are housed in an IP4X-rated enclosure to provide high protection against dust and contaminants.
- Enhanced Safety Measures: The switchgear includes a comprehensive interlocking system that meets the "five prevention" standards, preventing misoperation and enhancing operator safety. Additionally, pressure relief channels in the high-pressure compartment further ensure personnel safety.
- Convenient Operation and Monitoring: Each circuit breaker compartment is equipped with positioning and display devices, while an observation window on the front panel allows operators to monitor internal components without opening the cabinet.
- Environmental Adaptability: Designed for indoor use, the KYN28-12 switchgear can operate in ambient temperatures between -15°C and +40°C, with a maximum altitude of 4000m. It withstands high humidity levels and is built to resist seismic activity up to 8 degrees on the Richter scale.
Technical Specifications
- Rated Voltage: 12kV
- Rated Frequency: 50Hz
- Rated Current (Switchgear/Circuit Breaker): Up to 4000A
- Short Circuit Withstand Current: Up to 50kA (4s)
- Power Frequency Withstand Voltage: 42kV (pole-to-ground)
- Lightning Impulse Withstand Voltage: 75kV
- Protection Level: IP4X (IP2X when compartment door is open)
Applications
The KYN28-12 switchgear is suitable for a wide range of applications, including power plants, industrial facilities, and distribution stations. Its robust protection features and reliable performance make it ideal for high-demand environments requiring safe and efficient power distribution.
Ordering Information
When placing an order, please specify:
- Model and quantity.
- Primary and secondary schematic diagrams.
- Rated current and component specifications.
- Any special requirements for customization or additional safety features.
The KYN28-12 offers a powerful, safe, and adaptable solution for high-voltage power distribution, ensuring optimal performance and protection in critical energy networks.