Kyoritsu KEW6516
Yes
1 Year Warranty
Kyoritsu
Kyoritsu Kew6516
100, 250, 500, 1000 V
20.00/200.0/2000 MΩ
±2%
8 X 1.5 V Lr6 (AA) Batteries
Kyoritsu
UPS/DHL/FedEx
45*36*23cm
Japan
9030332000
Product Description
Designed for electrical installation professionals, the tester provides the tests required to verify the safety of commercial, industrial, and residential low-voltage electrical installations. Features continuous testing that can be carried out by use of the test button lockdown as well as three selectable test voltages: 250, 500, and 1000 V.





Features
- Color LCD 3.5" dot matrix
- Anti-trip technology (with 2 and 3 wire) for no trip LOOP L-PE testing on all RCDs
- With 2 wires only, very useful in case of no neutral (i.e. three-phase motor lines)
- High test current range of 2 Ω with 0.001 Ω resolution
- Zs Limit compares the values required by electrical installations standard with measured results
- Type AC, A, F, B (General and Selective), EV and Variable RCDs
- Single and auto test, ramp test and contact voltage
- Earth resistance test 2 and 3 wires with all accessories included
- Resistance test 100, 250, 500, and 1000 V with auto discharge voltage
- Continuity test at 200 mA or 15 mA with selectable buzzer for fast judgment
- On 3-phase lines with clear indication of the sequence on the display
- TRMS Voltage measurements 2 to 600 V, mains frequency
- Display shows how to connect the instrument according to the function selected
- Surge protection device test, for SPD that uses varistor
- Portable appliance tester function, for insulation and protective conductor resistance test
- IEC 61010-1 CAT IV 300 V, CAT III 600 V. IEC 61557-1, 2, 3, 4, 5, 6, 7, 10

What's included with the Kyoritsu KEW6516
- Tester
- Calibration Certificate
- Main Test Lead
- Test Leads with Remote Control Switch
- Distribution Board Test Lead
- Earth Resistance Test Leads
- Auxiliary Earth Spikes
- Soft Case
- Carrying Case
- Shoulder Strap
- Shoulder Pad
- 8 x LR6 (AA) Batteries
- USB Adaptor with KEW Report (Software)
- Instruction Manual
Large LCD and HELP function
- All the test data is shown in one large colored screen
- HELP function will show how to connect the instrument according to the function selected
Operation in three simple steps and hands free testing
- Set the rotary dial to your testing range
- Connect the instrument to the installation under test
- Press the test button (by remote probe or using the lockdown function of the test button)
Anti-trip technology (with 2 and 3 wire)
- For no trip LOOP L-PE testing on all RCDs
- With 3 wire (L, N, PE), to get the best accuracy readings
- With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines)
Loop impedance 0.001 resolution
- High test current range of 2 Ω with 0.001 Ω resolution
Insulation Resistance | |
Test Voltage | 100, 250, 500, 1000 V Maximum 1000 V (SPD) |
Measuring Ranges | 2.000/20.00/200.0 MΩ (auto-ranging) 20.00/200.0/1000 MΩ (auto-ranging) 20.00/200.0/2000 MΩ (auto-ranging) 0 to 1000 V (goes up by 1 V) (SPD) |
Accuracy | ±2% rdg ±6 dgt (2.000/20.00 MΩ); ±5% rdg ±6 dgt (200.0 MΩ) ±2% rdg ±6 dgt (20.00/200.0 MΩ); ±5% rdg ±6 dgt (1000 MΩ) ±2% rdg ±6 dgt (20.00/200.0 MΩ); ±5% rdg ±6 dgt (2000 MΩ) ±5% rdg ±5 dgt (SPD) |
Rated Current | 1.0 to 1.2 mA at 0.1 MΩ 1.0 to 1.2 mA at 0.25 MΩ 1.0 to 1.2 mA at 0.5 MΩ 1.0 to 1.2 mA at 1 MΩ |
Short Circuit Current | 1.5 mA maximum |
Loop Impedance | |
Function | LOOP ATT L-PE/L-N (3 wire) L-PE (2 wire) LOOP HIGH L-PE (0.01 Ω Res) L-PE (0.001 Ω Res) High test current (25 A) L-N/L-L |
Rated Voltage | 100 to 260 V (50/60 Hz) 48 to 260 V (50/60 Hz) 48 to 260 V (50/60 Hz) 100 to 260 V (50/60 Hz) 48 to 500 V (50/60 Hz) |
Impedance Range | 20.00/200.0/2000 Ω (auto-ranging) 20.00/200.0/2000 Ω (auto-ranging) 2.000 Ω 20.00 Ω |
Accuracy | ±3% rdg ±6 dgt ±3% rdg ±10 dgt ±3% rdg ±4 dgt ±3% rdg ±25 mΩ ±3% rdg ±4 dgt |
Nominal Test Current at 0 Ω External Loop: Magnitude/Duration at 230 V | L-N: 6A/60 ms; N-PE: 10 mA L-PE: 15 mA 20 Ω: 6 A/20 ms; 200 Ω: 0.5 A/20 ms; 2000 Ω: 15 mA/500 ms 25 A/20 ms 6 A/20 ms |
General Specifications | |
Applicable Standards | IEC 61010-1 CAT IV 300 V, CAT III 600 V Pollution degree 2 IEC 61010-2-034 IEC 61557-1, 2, 3, 4, 5, 6, 7, 10 IEC 60529 (IP40) IEC 61326 (EMC) |
Power | 8 x 1.5 V LR6 (AA) batteries |
Dimensions | 5.35 x 9.25 x 4.48" (136 x 235 x 114 mm) |
Weight | Approximately 45.85 oz (1300 g) including batteries |