Mobile Mine New Professional Supercomputing Container Is Fully Equipped and Plug and Play

Price Negotiable Compare
Min Order 2 Sets
Shipping From Guangdong, China
Popularity 265 people viewed
Quantity
+-
 

Guangzhou Ruisu Intelligent Technology Co., Ltd.

VIP   Audited Supplier 4 years
Profile Certified by SGS/BV
Orebox-RUISU-1200-4
ISO9001, CCC
Corrosion Resistance
as Custmer's Requirements
Q235 and Above Steel
Total Solution for Projects, 3D Model Design, Grap
Online Technical Support
Level a
20/40hq
Container Houses
Mobile Mining Farm for Bitcoin
128 Bit
Upper Limit: 1, 354 Kw
415VAC 3pH
NEMA 3 / IP54
336 Units with 3.25kw up to 4.0kw Power Consumptio
Air Economizer with Evaporative Cooling, 8 Panels
Ruisu
Using Standard Shipping Export Packaging
38.1 ft x 7.2 ft x 7.5 ft
Mainland, China
Product Description

The Specification of Ore Box- RUISU-1200 Mining Enclosure
 
ModelOre Box- RUISU-1200 Mining Enclosure
 
DimensionsEnclosure Length x Width x Height  38.1 ft x 7.2 ft x 7.5 ft
Number of installed mining rigs   336 units with 3.25kW up to 4.0kW power consumption per rig
 
Enclosure rating
 
NEMA 3 / IP54
 
Power
Power
Power Input KW
 
Upper Limit: 1,354 KW
 
Input Voltage
 
415VAC 3ph
 
Inside Access
 
3 phase power connection to inside access 4 Main Breakers
 
Connection type
 
3 Hot wires, 1 Neutral, 1 Ground, each phase Volts: 415VAC / 240VAC
 
Distribution Panel and Breakers
 
Each cabinet has 4 power distribution  panel. Each distribution panel: 1 x 600A 3-pole molded case main circuit breaker, 4 x 175A 3-pole molded case circuit breaker, 84 x 20A 1P circuit breaker, 6x6A 3P circuit breaker, 1x10A 2P circuit breaker, 3x20A 2P circuit breaker, 1x32A 4P circuit breaker, 1xSPD 40 (3L+N) surge protector
 
Power Distribution & Cabling
 
1. Power distribution unit: main panel circuit breaker (Schnei der), distribution circuit breaker (Nader), contactor (Nader).
  1. Equipment and rack: Ore Box installation rack, UL standard Ore Box power socket, lighting, cooling fan.
  2. All wiring: use cable (mining cable UL1015 10/12/14 AWG)
Including the outlet from the circuit breaker of the distribution panel to the power socket of the miner, the Y-type pigtail can be ordered separately to connect the dual miner plug input to the power socket. The lighting and cooling fans are installed in the container and can be used directly.
CoolingCooling technology
 
Air Economizer with Evaporative cooling, 8 Panels per Container
 
Industrial grade Exhaust Fans (550W per fan)
 
16 Fans with automated louvers
 
Airflflow (Cubic-Feet-per-Minute)
 
376,000 CFM (638,828 Cubic Meter/Hour)
 
Air filtering system
 
Include air filter net  and dust filter net
Additional technical detailsSecurity Key locks standard to dual entry/egress security doors
 
Regulatory complianceUL 489, Compliant to IEC 60950 and international wiring regulations
 
External Environmental Operation limitsOperating temperatures40°F to 115°F
 
Operating humidity range 0 to 90% RH (below Condensation point)
 
Operating altitude0 to 5,000 ft
 





Message Type