Product Description

RM60 3PH Rack Module UPS

KEY FEATURES

  1. Power Module 60K Rack Module UPS 120K/180K/240K/300K/480K/600K
  2. High effciency over 94.5% at 50% load, Output Power Factor 1 technology
  3. DSP control, ,online double conversion,Integrated modular and parallel technology
  4. High scalability,Single rack expanding 120KVA to 600KVA, N+1 or N+X redundancy in the same rack, supports 1+1 cabinet parallel operation.
  5. Built-in maintenance bypass, praevia all panel control and connectors
  6. Highly reliable operation with redundant power supply in STS
  7. High overload Capacity ,  60mins@110%, 10Mins@125% ,1mins@150%
  8. 32 to 40PCS adjustable Battery numbers
  9.  Adiustable charging current,Max 18A


TECHNICAL SPECIFICATIONS

MODELRM120/60X30U-RYYRM180/60X30U-RYYRM240/60X-RYYRM300/60X-RYYRM480/60X42U-RYYRM600/60X42U-RYY
PHASE3-phase in/3-phase out
CABINET CAPACITY*120KW180KW240KW300KW480KW600KW
BATTERY TYPEExternal Battery
One Power Module Capacity60KVA/60KW
Max. Power Module No.2345810
INPUT
Nominal Voltage380VAC/400VAC/415VAC (3Ph+N)
Voltage Range305 ~ 478 VAC at 70% - 100% load; 208 ~ 478VAC for <70% load
Nominal Frequency50/60Hz (Auto sensing)
Frequency Range40Hz ~70Hz
Power Factor> 0.99 at 100% load, >0.98 at 50% load
Harmonic Distortion (THDi)< 3% @ 100% load
OUTPUT
Nominal Voltage380VAC/400VAC/415VAC (3Ph+N)
Voltage Regulation      (Steady State)<=± 1% Typical (balanced load)
<=± 2% Typical (unbalanced load)
Nominal Frequency50/60Hz
Frequency Range (Synchronized Range)46Hz ~ 54Hz or 56Hz ~ 64Hz
Overload Capability110% for 1 hour,  125% for 10 mins  , 150% for 1 min  and 200ms for >150%
Harmonic Distortion<= 2% THD (Linear Load)
<= 4% THD (Non-linear Load)
EfficiencyUp to 96%
BATTERY / CHARGER
Nominal Voltage+/-  192V~+/- 240V  (Selectable)
Maximum Voltage+/- 240V (12V x 40 Pcs)
Minimum Voltage+/- 192V (12V x 32 Pcs)
Floating Charge Voltage2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage2.35V/Cell
Temperature CompensationYes
Maximum Charging Current (Per Power Module)18A
PHYSICAL
Cabinet Dimension
(D x W x H) mm
1100 x 600 x 14751100 x 600 x 20101065 x 1000 x 2000
Net Weight (kgs)3083525165169321020
ENVIRONMENT
Operation Temperature0 ~ 40ºC
Relative Humidity0 ~ 95% non-condensing
Altitude*<1000m for Nominal power
IP ClassIP 20
MANAGEMENT
RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
STANDARDS
SafetyIEC/EN 60950-1; IEC/EN 62040-1
EMCIEC/EN 62040-2 Category C3

*If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.