TX
Water-Cooled
Water-cooled
Integral
Ultra Quiet
Hot Water Absorption Chiller
LUCY
CE
Qingzhou, Shandong
8418692090
Product Description

1. The lowest working temperature of hot water is 75 degrees centigrade.
2. The above unit includes lithium bromide absorption chiller, control box, cooling water tower, chilled water pump, cooling water pump, hot water adjusting valve, filter of chilled & cooling water, vacuum pump.
3. Fouling factor for chilled water is 0.086m2 degrees centigrade/KW.

Model | TX-175 | |
Cooling capacity Kw | 175 | |
Hot water | Flow rate m3/h | 42.8 |
Inlet/Outlet Temp | 90 / 85 ºC | |
Inlet/Outlet Dia. | DN80 | |
Pressure loss MPa | 0.05 | |
Chilled water | Flow rate m3/h | 30.0 |
Inlet/Outlet Temp | 15 / 10ºC | |
Inlet/Outlet Dia. | DN65 | |
Pressure loss MPa | 0.05 | |
Dimension | Length mm | 3000 |
Weight mm | 1780 | |
Height mm | 2450 | |
Electrical consumption Kw | 10 | |
Shipping weight Kg | 4100 |
1.
The above unit includes lithium bromide absorption chiller, control box, cooling water tower, chilled water pump, cooling water pump, hot water adjusting valve, filter of chilled & cooling water, vacuum pump.
2.
Fouling factor for chiller water is 0.086m2ºC/Kw.
3.
Refrigeration standard of the climate conditions: Atmospheric temperatures 36 ºC,Wet bulb temp: 27ºC.