Sanhe SHVC intelligent permanent magnet vacuum contactor, as a new generation of medium voltage vacuum contactor, is fitted a permanent magnet mechanism to close/open the dynamic and static contacts of the vacuum interrupter in a direct motion. SHVC intelligent permanent magnet vacuum contactor can be widely used in the three-phase AC system below 12kV and rated frequency 50Hz/60Hz where multiple opening and closing operation cycles are required, and it is especially suitable for users who operate frequently. SHVC intelligent permanent magnet vacuum contactor adopts a wide-voltage, high-efficiency and reliable electronic control module, and uses STM32 mainstream chips inside. It has the characteristics of fast response to closing and opening, LED indication for closing and opening, and alarm auxiliary contact output.
SHVC intelligent permanent magnet vacuum contactor has the characteristics of energy saving, material saving, fireproof, explosion-proof, small size, long life, low maintenance cost, reliable operation and no pollution. It is widely used in the control and protection of power transmission and distribution systems in the fields of electric power, machinery, metallurgy, mining, petroleum, chemical industry, railway, broadcasting, communications, and transportation. Using the ideal technology of breaking current in a vacuum environment, as well as extremely high reliability and compact structure, the contactor can be used under particularly harsh conditions. They are suitable for control and protection (with fuses) circuits, substations and distribution stations, motors, transformers, capacitor banks, etc.
Features:
Main features of SHVC intelligent permanent magnet vacuum contactor are as follows:
maintenance free
reliable vacuum technology
frequent operation support
monostable permanent magnet actuator
long electrical and mechanical life
wide voltage power supply module
small closure value
compact structure
Specification Sheet
Conditions:
SHVC intelligent permanent magnet vacuum contactor can be used normally under the following environmental conditions:
Ambient temperature: -25ºC~+40ºC
Relative humidity: ≤95% (daily average); ≤90% (monthly average)
Altitude: ≤2000m (SHVC-7); ≤1000m (SHVC-10, SHVC-15)
Water vapor pressure: ≤2.2×10-3Pa (daily average); ≤1.8×10-3Pa (monthly average)
The surrounding air should not be significantly polluted by corrosive or flammable gas, water vapor, etc.
No frequent severe vibration
During operation, the inclination angle between the installation plane and the horizontal plane is not over 5°
Reference &Executive standards
SHVC intelligent permanent magnet vacuum contactor complies with the standards of most industrial countries and fully complies with the following standards:
IEC 62271-106:2011 High-voltage switchgear and controlgear-Part 106:Alternating current
contactors, contactor-based controllers and motorstarters"
IEC 60282-1:2020 High-voltage fuses-Part 1: Current-limiting fuses
GB/T 14808-2016 "High-voltage AC contactor, contactor-based controller and motor starter"
GB 16926-2016 "High-voltage AC load switch-fuse combination electrical appliance"
GBT 11022-2011 "Common technical requirements for high-voltage switchgear and control equipment standards"
GB/T 15166.2-2008 "High Voltage AC Fuses Part 2: Current Limiting Fuses"
JB 7122-2007 "Basic requirements for AC vacuum contactors"
Standard fitting


SHVC intelligent permanent magnet vacuum contactor has the characteristics of energy saving, material saving, fireproof, explosion-proof, small size, long life, low maintenance cost, reliable operation and no pollution. It is widely used in the control and protection of power transmission and distribution systems in the fields of electric power, machinery, metallurgy, mining, petroleum, chemical industry, railway, broadcasting, communications, and transportation. Using the ideal technology of breaking current in a vacuum environment, as well as extremely high reliability and compact structure, the contactor can be used under particularly harsh conditions. They are suitable for control and protection (with fuses) circuits, substations and distribution stations, motors, transformers, capacitor banks, etc.
Features:
Main features of SHVC intelligent permanent magnet vacuum contactor are as follows:
maintenance free
reliable vacuum technology
frequent operation support
monostable permanent magnet actuator
long electrical and mechanical life
wide voltage power supply module
small closure value
compact structure
Specification Sheet
Technical data | SHVC-7P-200/400/630 | SHVC-10P-200/400/630 | |
Rated voltage | Ur(kV) | 7.2 | 12 |
Rated current | Ie(A) | 200/400/630 | 200/400/630 |
Rated frequency | fr(Hz) | 50-60 | 50-60 |
Rated short-time withstand current | Ik(kA) | 4 | 6.3 |
Rated peak withstand current | Ip(kA) | 10 | 16 |
Rated short circuit breaking current | Io(kA) | 4 | 5 |
Rated short-circuit making current | Ic(kA) | 10 | 12.5 |
capacitive switch current | Itc(A) | 230 | 230 |
Operating frequency | (Times/hour) | 900 | 900 |
Mechanical life | (Times) | 30×104 | 30×104 |
Electrical life | (Times) | AC-3:25×104 | AC-3:25×104 |
(Times) | AC-4:10×104 | AC-4:10×104 | |
Rated lightning impulse withstand voltage | Up(kV) | 60 | 75 |
Rated power frequency withstand voltage (1min) | Ud(kV) | 32 | 42 |
Three-phase closing synchronization | (ms) | ≤2.0 | ≤2.0 |
Contact bounce time | (ms) | ≤5.0 | ≤5.0 |
Conductive loop resistance of each phase (20ºC) | (μΩ) | ≤180 | ≤180 |
Control loop | |||
Control module- rated operating voltage | Ur(V) | 110V/220V(AC,DC) | |
Rated operating voltage range | (V) | 0.85Ur~1.1Ur | |
Latching mode | Permanent magnet | ||
Operating power | DC110V,3A | ||
DC220V,1.5A | |||
AC220V,1A | |||
Closing time | (ms) | ≤50 | |
Inherent opening time | (ms) | ≤20 | |
1min power frequency withstand voltage | (kV) | 2 | |
Auxiliary contacts-quantity | 5 open 5 close | ||
Conventional heating current | (A) | 6 | |
Mechanical life | (Times) | 5×106 | |
Electrical life | (Times) | 2×106 | |
Rated working current | DC/AC110V,0.4A | ||
DC/AC220V,0.2A |
SHVC intelligent permanent magnet vacuum contactor can be used normally under the following environmental conditions:
Ambient temperature: -25ºC~+40ºC
Relative humidity: ≤95% (daily average); ≤90% (monthly average)
Altitude: ≤2000m (SHVC-7); ≤1000m (SHVC-10, SHVC-15)
Water vapor pressure: ≤2.2×10-3Pa (daily average); ≤1.8×10-3Pa (monthly average)
The surrounding air should not be significantly polluted by corrosive or flammable gas, water vapor, etc.
No frequent severe vibration
During operation, the inclination angle between the installation plane and the horizontal plane is not over 5°
Reference &Executive standards
SHVC intelligent permanent magnet vacuum contactor complies with the standards of most industrial countries and fully complies with the following standards:
IEC 62271-106:2011 High-voltage switchgear and controlgear-Part 106:Alternating current
contactors, contactor-based controllers and motorstarters"
IEC 60282-1:2020 High-voltage fuses-Part 1: Current-limiting fuses
GB/T 14808-2016 "High-voltage AC contactor, contactor-based controller and motor starter"
GB 16926-2016 "High-voltage AC load switch-fuse combination electrical appliance"
GBT 11022-2011 "Common technical requirements for high-voltage switchgear and control equipment standards"
GB/T 15166.2-2008 "High Voltage AC Fuses Part 2: Current Limiting Fuses"
JB 7122-2007 "Basic requirements for AC vacuum contactors"
Permanent Magnet Structure

Standard fitting