Product Description
Chapter 1. General introduction
The ABT series intelligent temperature controller can be applied in the control and alarm in a range of -200 ~ 2300ºC. It can use in the controller and alarm of pressure, discharge, liquid level, humidity, etc, parameters when fitted with the corresponding transmitter.
The key features include
1. 18 kinds of input signals including signals of thermocouple, resistance thermometer detector (RTD), direct voltage, and direct current can be input freely.
2. Freely changeable with on-off control or PID control with configurable direct reverse action modes. It has the self-tuning function of PID parameter.
3. Control output supports relay contact switch, solid-state relay (SSR) driving voltage, single-phase thyristor zero-crossing trigger signal, direct voltage, and direct current.
4. One way of programmable alarm outputs is provided with a number of alarm modes including higher limit, and lower limit. In addition, the alarm features can also be temporarily disabled when applying power.
5. Comprehensive self-detection and protection-- In case of error, it provides automatic repair or prompt message and closes the output.
Chapter 2.Model and definition

Chapter 3.General parameters
The ABT series intelligent temperature controller can be applied in the control and alarm in a range of -200 ~ 2300ºC. It can use in the controller and alarm of pressure, discharge, liquid level, humidity, etc, parameters when fitted with the corresponding transmitter.
The key features include
1. 18 kinds of input signals including signals of thermocouple, resistance thermometer detector (RTD), direct voltage, and direct current can be input freely.
2. Freely changeable with on-off control or PID control with configurable direct reverse action modes. It has the self-tuning function of PID parameter.
3. Control output supports relay contact switch, solid-state relay (SSR) driving voltage, single-phase thyristor zero-crossing trigger signal, direct voltage, and direct current.
4. One way of programmable alarm outputs is provided with a number of alarm modes including higher limit, and lower limit. In addition, the alarm features can also be temporarily disabled when applying power.
5. Comprehensive self-detection and protection-- In case of error, it provides automatic repair or prompt message and closes the output.
Chapter 2.Model and definition

Chapter 3.General parameters
v TInput Type | Code | Measuring range | Input Type | Code | Measuring range |
Thermocouple (TC) | K | -100ºC ~ +1350ºC | Resistance thermometer detector (RTD) | Cu50 | -50ºC ~ +150ºC |
S | -50ºC ~ +1750ºC | Pt100 | -200ºC ~ +850ºC | ||
R | -50ºC ~ +1750ºC | DC Voltage (U) | 0 - 5V | Customized range within -1999 ~ +9999 | |
T | -200ºC ~ +400ºC | 1 - 5V | |||
E | -100ºC ~ +1000ºC | 0 - 10V | |||
J | -100ºC ~ +1200ºC | DC Current (I) | 0 - 20mA | ||
B | 600ºC ~ +1800ºC | 4 - 20mA | |||
N | -100ºC ~ +1300ºC | ||||
L | -100ºC ~ +800ºC | ||||
WRe3-WRe25 | 0ºC ~ +2350ºC | ||||
WRe5-WRe26 | 0ºC ~ +2350ºC |
3.2 Accuracy of measurement: class 0.2 (± 0.2% FS ± 0.1ºC). Thermocouple Cold-end Compensation deviation: ± 2ºC
3.3 Sampling period: 0.25s
3.4 Control period: 1 ~ 120s (free set)
3.5 Control modes (free changeable)
ON/OFF control(configurable direct/reverse action and differential gap)
PID control (configurable direct/reverse action, manual or automatic configuration of PID parameters)
3.6 Output specifications
Relay contact switch output: 250VAC/2A, 30VDC/2A
Solid-state relay (SSR) driving voltage output: 5 ~ 12VDC/25mA
Single-phase thyristor zero-crossing trigger signal: 85 ~ 264V/50 ~ 60Hz, capable of triggering 5 ~ 500A TRIAC or 2 SCRs in inverse parallel connection or thyristor power module.
DC current output: 0 - 5V, 1 - 5V switchable output linearity ≤ 0.5%, output load resistance ≥ 1kΩ, electrically isolated from signal inputs and auxiliary power supply.
3.7 Alarm mode (free switchable)
Five kinds of alarm modes: Higher absolute values, lower absolute values, higher limit deviation values, lower limit deviation values, and higher and lower limit deviation values. Besides, it can set the releasing alarm characteristics when the instrument is powered on to avoid alarm misoperation when powered on.
3.8 Working power supply: 220V ± 10% / 50 ~ 60Hz, power consumption < 3W
3.9 Operational environment: places free of corruption with a temperature of 0 ~ 50ºC, and relative humidity ≤ 85% RH
Chapter 4. Shape and Hole cutout dimension
3.3 Sampling period: 0.25s
3.4 Control period: 1 ~ 120s (free set)
3.5 Control modes (free changeable)
ON/OFF control(configurable direct/reverse action and differential gap)
PID control (configurable direct/reverse action, manual or automatic configuration of PID parameters)
3.6 Output specifications
Relay contact switch output: 250VAC/2A, 30VDC/2A
Solid-state relay (SSR) driving voltage output: 5 ~ 12VDC/25mA
Single-phase thyristor zero-crossing trigger signal: 85 ~ 264V/50 ~ 60Hz, capable of triggering 5 ~ 500A TRIAC or 2 SCRs in inverse parallel connection or thyristor power module.
DC current output: 0 - 5V, 1 - 5V switchable output linearity ≤ 0.5%, output load resistance ≥ 1kΩ, electrically isolated from signal inputs and auxiliary power supply.
3.7 Alarm mode (free switchable)
Five kinds of alarm modes: Higher absolute values, lower absolute values, higher limit deviation values, lower limit deviation values, and higher and lower limit deviation values. Besides, it can set the releasing alarm characteristics when the instrument is powered on to avoid alarm misoperation when powered on.
3.8 Working power supply: 220V ± 10% / 50 ~ 60Hz, power consumption < 3W
3.9 Operational environment: places free of corruption with a temperature of 0 ~ 50ºC, and relative humidity ≤ 85% RH
Chapter 4. Shape and Hole cutout dimension
Panel Dimension Code | Panel dimension | Case dimension | Hole cutout dimension | ||||
W | H | W | H | D | W | H | |
A | 96 | 96 | 91 | 91 | 80 | 92 | 92 |
D | 72 | 72 | 67 | 67 | 80 | 68 | 68 |
E | 48 | 96 | 44 | 90 | 80 | 45 | 92 |
F | 96 | 48 | 90 | 44 | 80 | 92 | 45 |
G | 48 | 48 | 44 | 44 | 80 | 45 | 45 |