PR240 series
Digital Automatic Control
Motor Protect
3
Ac
3
Medium Power Relay
Enclosed Relay
Electromagnetic Type
Miniature
Electric Parameter Relay
N/a
5A 250V
Blue Jay
Please Consult with Us for More Detail Information
10*10cm
Chongqing, China
Product Description

PR 240 electronic motor protection relay is an excellent choice for telemetry applications to monitor, meter and control Motor. Its small size, low cost and remote HMI options make the relay a perfect option for power distribution systems to be used in end-of-line monitoring and power metering.
PR240 motor temperature protection relay offers low-voltage motor protection in almost all applications, including pumping, air-based, chiller, and bulk-material applications. The motor thermal relay can be configured as full range of medium-voltage, three-phase induction and synchronous motors protect relay.
* Panel mounting HMI unit and Din-rail mounting control unit
* Suitable for Motor under 0.66KV and any current range
* HMI unit provides 3-phase current voltage monitors, Power Measurement
* Control unit builds in 200A CT, out of range use .../5A CT connect
* Abundant protection modes can be freely selected to alarm or trip
* Can select a variety of startup modes for different wiring application
* RS-485 network communications
* 4 digital outputs, and 7 digital inputs
* Optional 1 programmable analog output
* Suitable for Motor under 0.66KV and any current range
* HMI unit provides 3-phase current voltage monitors, Power Measurement
* Control unit builds in 200A CT, out of range use .../5A CT connect
* Abundant protection modes can be freely selected to alarm or trip
* Can select a variety of startup modes for different wiring application
* RS-485 network communications
* 4 digital outputs, and 7 digital inputs
* Optional 1 programmable analog output

The working environment of PR 240 Intelligent Motor Management Relay
Motor-rated voltage: | AC380V / AC660V |
Motor rated current: | 0.5-820A |
Working temperature: | -10C ~ +55C |
Storage temperature: | -25C ~ +70C |
Relative humidity: | < 93% RH |
Elevation: | not more than 3000 m |
Atmospheric conditions: | installation site does not allow the explosive medium, containing gas to corrode metal and damage the insulation and conductive medium. |
Measuring accuracy of PR 240
Current: | ± 0.5% @ 10% to 200% of Ie |
Voltage: | ± 0.5% @ 10%~150%Ue |
Frequency: | ± 0.1% @ 45 ~ 65Hz |
Power factor: | ± 1.0% @ 0 ~ 1.000 |
Active Power | ± 1.0% @ 0 ~ 500kW |
Leakage current: | ± 1% @10% to 100% of Ir |
Analog Output: | ± 1% @4 ~ 20mA |
Electrical parameters of PR 240 Motor Protector
Auxiliary Power: | AC90-240Vac/dc |
Power consumption: | <10 VA |
Insulation resistance: | > 100MΩ |
Relay: | Alarm relay @ 5A / 250VAC, 5A / 30VDC (NO node) |
Electrical test of PR 240 Motor Protection Relay:
IEC 61000-4-2 | level III |
IEC 61000-4-4 | level III |
IEC 61000-4-5 | level III |
IEC 61010-1 | AC2kV/1min Between power / input / output |