Product Description

Arc protection relays are mainly used to detect arc faults in electrical systems and protect equipment and personnel in electrical systems from arc faults. Arc protection relays can detect arcs by monitoring parameters such as current, voltage, and electric power, and quickly disconnect the power supply before an electrical fire occurs, thereby reducing the risk of fire.
Arc protection relays are usually used in medium and high-voltage power distribution systems, control cabinets, transformers, generators, motors and other electrical equipment. They adopt the dual-criteria principle of arc light detection and overcurrent detection and have the characteristics of fast protection action and high reliability.
* Complete digital design, simple principle;
* Strong electrical performance;
* Comprehensive record of fault information;
* Double criterion of over-current and arc, high reliability;
* Optical fiber transmits, strong electromagnetic interference resistance;
* Programmable logic of trip exit;
* Fast exit tripping, short total fault clearing time.
* Strong electrical performance;
* Comprehensive record of fault information;
* Double criterion of over-current and arc, high reliability;
* Optical fiber transmits, strong electromagnetic interference resistance;
* Programmable logic of trip exit;
* Fast exit tripping, short total fault clearing time.

AFR-S | AFR-M12 | AFR-M24 | AFR-M36 | AFR-M48 | |
Basic parameter of arc flash relays | |||||
Power supply | 85~265Vac/dc, optional 48Vdc | ||||
Consumption | Monitoring Stanby <5W DO trig <10W | Monitoring Stanby <8W DO trig <10W | |||
Rated current (In) | 5A or 1A | ||||
Protection range | 0~20 In | ||||
Burden | 0.5VA | ||||
Protect current accuracy | <2% | ||||
Protect frequency accuracy | 0.1Hz | ||||
Arc signal & control | |||||
Sensor type | lens point fiber optic sensors(1) or bare fiber optic sensors(2) | ||||
Arc sensor access channels | 3 | 12 | 24 | 36 | 48 |
DO relay channels | 6 | 4 | 4 | 9 | 9 |
Trip coil contact | AC250V/8A fast relay, passive node | ||||
Trip operation time | <10ms @ only arc protection | ||||
<20ms @ overcurrent + arc protection | |||||
Safety isolation | 2500V isolation capacity | ||||
Binary inputs | 5 | 12 | 12 | 16 | 16 |
Others | |||||
Comm port | RS485 MODBUS-RTU | 1* RS485 MODBUS-RTU 1* 10/100M Adaptive Default 192.168.12.2/192.168.13.2 IEC-60870-5-103 | |||
SOE record | 512 | 512 | 512 | 512 | 512 |
Waveform capture | / | 8 | 8 | 8 | 8 |
Optional modules | Wireless joints temperature monitor Smoke detector |