3W3G10-40K
Three Phase
On-line
Overvoltage
Communication
Lighting/Power
Long-acting Machine
Sine Wave Output UPS
Large Type
Decentralized
Customization
Yes
Optional
1.0
Yes
External
Rack Mounted and Tower Design
Support Self-Gravity Induction
Reros
Carton
10-40kVA
China
85044020
Product Description
3W3G10-40Kva
Main feature
1.Output PF up to 1.0, compatible with rack/tower installation;
2. Charging current 1-13A can be set.
3. Input power factor >0.99, input current harmonic <3%
4. Equipped with 4 inch 16.5M color IPS capacitive touch screen
5. LCD screen rotation design, support self gravity induction
6. ECO mode with high efficiency
7. RS232/RS485/USB communication port
8. Intelligent SNMP( optional )
Application
1.Data center
2.IT room
3.Commercial facility
4.Precision instrument
5.Telecom system
6.Rack device
Specification
Model | 3W3 G10K | 3W3 G15K | 3W3 G20K | 3W3 G30K | 3W3 G40K | ||||
Capacity | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | ||||
Input features | |||||||||
Input voltage(Vac) | 380±20% | ||||||||
Frequency ( HZ ) | 50HZ±5HZ | ||||||||
Phase | 3 Phase 4 Wires+ Ground | ||||||||
Power Factor | ≥0.99 | ||||||||
Battery voltage ( Vdc ) | ±192 | ||||||||
Battery quantity ( PCS ) | 32-40 can be adjustable | ||||||||
Battery type | External | ||||||||
Output features | |||||||||
Power Factor | 1.0 | ||||||||
Output voltage ( Vac ) | L-N:220±1% L-L:380±1% | ||||||||
Frequency ( HZ ) | 50Hz/60Hz±0.2% | ||||||||
Transfer time ( ms ) | 0 | ||||||||
Efficiency( AC mode at full loads) | ≥96% | ||||||||
N+X in parallel ( PCS) | 3 | ||||||||
Waveform | Linear Load THD<3%; Non-linear Load THD<5% | ||||||||
Overload capacity | 125%full load keep 10min; 150%full load keep 1min; | ||||||||
Crest factor | >3:1 | ||||||||
Others | |||||||||
Manual maintenance bypass | with no transfer time bypass maintenance switch | ||||||||
Communication | RS232/RS485/dry contact(SNMP/USB are optional) | ||||||||
Protection | Output short circuit protection, output overload protection, over temperature protection, battery low-voltage protection, output over under-voltage protection, fan fault protection, etc | ||||||||
Alarm | Battery low-voltage, mains abnormal, overload, UPS fault, over temperature protection | ||||||||
Communication port | Standard:RS232,RS485,Dry contact,USB;For optional:SNMP | ||||||||
Display | 4 inches touchable screen | ||||||||
Working temperature | 0~55ºC | ||||||||
Humidity | 0%-95%(No condensing) | ||||||||
Noise(dB) | <65dB(Within 1 meter) | ||||||||
Size(D×W×H) (mm) | 680×440×133(3U) | 750×440×133 | |||||||
Weight(KG) | 25 | 28 | 32 | 36 | 38 |