Rectifier System -48V/ 600A with Indoor Cabinet

Price Negotiable Compare
Min Order 1 Piece
Shipping From Guangdong, China
Popularity 487 people viewed
Quantity
+-
 

Shenzhen Gold Power Tech Co., Ltd.

VIP   Audited Supplier 18 years
Profile Certified by SGS/BV
GP48600H
Single
2 Years
36kw
Full Range
Parallel Switching Power Supply
Separate-excited Switching Power Supply
Width Modulation Type
Terminal Power Distribution Equipment
One-way Transmission
PWM
CE, RoHS, ISO, CCC, CB
Gold Power
GOLD POWER
Wood Packing
600X600X1600mm
China
8504401990
Product Description
                        Rectifier System -48V/ 600A with Indoor Cabinet

GP48600H Cabinet Power System         
 Input: 90~280Vac; Output: -42~-58Vdc

Main features:
1.Adoption of active power factor compensation technology with factor up to 0.99
2.Wide operating range of AC input voltage: 90~290Va
3.Adoption of full bridge soft start with efficiency more than 92%
4.Perfect battery management, battery temperature compensation, LVLD and LVBD protection, secondary shutdown, automatic voltage regulation, automatic control on equalizing/float charge, on line battery test
5.Hot-swappable, the time for replacement is less than 1 min.
6.Multiple communication port (RS485, PFC), locol & remote control available, non-attendant
7.Excellent lightning design applicable to thunder stormy areas
8.Failure protection and alarm
9.Operation & maintenance front-accessible, wall-mounted makes room saving ,Low radiation
10.System is of high reliability and EN60950 , GB4943 compliance











 
The system consists of distribution unit, rectifier module (Minimum 1 piece) and 1 monitoring module. As following table:
 
ConfigurationRectifier ModuleMax. DistributionMonitoring ModuleRemark
Option GPR4850D12AC distribution: 3 phases, 5 wires input, Class II/C SPDs;
3-pole AC input MCB 63A
Single-pole breaker @ rectifier input (20A*12)
AC output MCB: 3*16A(1P) 1*32A (3P)
DC distribution: Battery fuse 250A*2;
LVD1: 16*32A,8*63A
LVD2: 5*16A, 5*32A, 3*63A
GPM48AFor details, please refer to the specifications of modules.
 
Input
ParameterMin.TypicalMax.UnitRemark
 Operating voltage rating 110/220 Vac 
Input voltage range90220290Vac3 phases, 5 wires input,
Ph-Ph: 380V,
Ph-Neutral line: 220VAC
Input frequency435067Hz 
Battery input43.253.558Vdc"+""-" of the battery group connected in parallel with DC output of rectifier module. (With identical polarity)
 
Output
ParameterMin.Typical Max.UnitRemark
Output voltage range4253.558Vdc 
Output current range (Max current)0 600A170~285Vac input;
The derating will be adopted for input voltage below 170Vac.
Regulation  ±1% 
Load regulation  ±1% 
Line regulation  ±1% 
Current sharing  ±5% 
Battery output  250A*2  
Ripple (Vp-p)  200mvRated input/output, with 0.1uF film capacitor and 10uF high frequency electrolyte capacitor, oscilloscope band width of 20MHz.
Output efficiency9193 %220Vac input