AID120
IEC61557
Anti-static
Embedded
LED
DC24V
0.6W
Acrel
Carton
172*87*158
China
Product Description
AID120 Alarm and Display Device
It is fit for embedding into operating room or nurse station internal wall installation which can monitor one set of AIM-M100 insulation monitoring device with the function of sound-light alarm on failures like insulation, overload, overtemperature and equipment failure etc. and digital display and RS485 communication.
AID120 is usually combined with AIM-M100, AID120 is usually used in combination with AIM-M100 for data exchange through RS485 communication.
- The insulation resistance alarm value, load current alarm value and transformer temperature alarm value of each system insulation monitoring instrument can be set up remotely.
- When there are insulation faults, overload, excessive temperature rise of the voltage transformer or wiring faults in any of the monitored system, centralized alarm and display instrument can provide corresponding sound and light alarm function, and can manually eliminate the alarm sound.
4. Parameters
AUX POWER | Voltage | DC 24V |
Power consumption | ≤0.6W | |
Insulation measure range | 10…999kΩ | |
Insulation alarm range | 50…999kΩ | |
Transformer Load Rate | Percentage display | |
Current alarm range | 14A,18A,22A,28A,35A,45A | |
Temperature alarm range | 0…+200ºC | |
Alarm mode | Sound and light alarm | |
Alarm type | Insulation fault, overload, overtemperature, equipment failure | |
Communication mode | RS485,MODBUS-RTU | |
Display mode | LCD liquid crystal display,128*64 dot array |
5. Installation