ME231
1 Year
1 Year
Digital
DIN Rail Mounting
Multi-Functional Energy Meter, Watt-Hour Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Reactive Energy Meter, Multi-rate Watt-hour Meters, Maximum Demand Meter, Power Analyzer
Three-phase Four-wire
Electronic Meter
Terminal Type
Cts and Rogowski Coil
Energy Meter
RoHS, ISO, CE
Customized
600V Version / High Voltage Version
External Cts, External Rogowski Coil
Touch Button
1.77 Inch TFT Screen Display
220V AC (95-265VAC), 24V DC
Alarm, 6 Tariff
Modbus RTU, RS485 Port
3pH4w 3pH3w 1pH2w (L-N) 1pH2w(L-L) 1pH3w(L-L-N)
0-600VAC
Class 0.5s
50/60Hz
8K Samples Per Second
50th Max
2400BPS ~ 38400BPS
Adjustable From 0.1A to 9999A
MEATROL
Poly Bag and Stand Export Carton
9.45*7.25*6.6CM
China
9030331000
Product Description

World-famous manufacturer
Three major production bases in Shanghai, Chongqing, and Zhejiang
Looking forward to in-depth communications, project cooperation, and exclusive agency
Contact: Susan
Three major production bases in Shanghai, Chongqing, and Zhejiang
Looking forward to in-depth communications, project cooperation, and exclusive agency
Contact: Susan


Current sensors for reference, more options could be offered.
RATED CURRENT | CURRENT SENSOR | DESCRIPTION |
5A | SCT-10 | Diameter 10mm |
50A | SCT-16 | Diameter 16mm |
100A | MRC-16 | Diameter 16mm (Rogowski coil) |
300A | MRC-24 | Diameter 24mm (Rogowski coil) |
600A | MRC-36 | Diameter 36mm (Rogowski coil) |
1kA | NRC-100 | Diameter 100mm (Rogowski coil) |
3kA | NRC-150 | Diameter 150mm (Rogowski coil) |
6kA | NRC-200 | Diameter 200mm (Rogowski coil) |

The ME231 is a DIN-Rail three-phase multifunctional smart meter that supports externally connected with open type Rogowski coil or voltage type CT, it can realize none dismantling wire test, simplify test steps, save construction cost, and is more convenient for engineering test as well as the inspection and maintenance of distribution system.
The ME231 support systems of single-phase and three-phase. It can measure multiple electrical parameters such as current, voltage, power factor, harmonics, power, energy and other electrical parameters of L1,L2,L3.The standard RS485 communication interface can be compatible with various configuration systems through the standard MODBUS-RTU protocol.
1.Product features
Description | ||
Type | DIN rail | |
Model | ME231 | |
Current sensor type | Rogowski coil Voltage-output current clamp | |
Advantage | Suitable for wide current range, no dismantling measurement | |
Wiring system | 3P4W 4CT,3P4W 3CT,3P3W 3CT,3P3W 2CT,1P3W,1P2W | |
Application field | Power analysis Tariff meter | |
Display screen | 1.77 inch TFT screen display | |
Weight | 259g | |
Dimension | L*W*D: 9.45*7.25*6.6CM | |
Color | White | |
Current | ||
Channel input voltage range | 0-900mVAC peak,636 mV RMS | |
Measurement range | Different current sensors have different ranges | |
Rcoil | 50mV/kA@50Hz(0-12000A),@60Hz(0-10000A) 85mV/kA@50Hz(0-7000A),@60Hz(0-6000A) ... | |
VCT | 0~99999A | |
Voltage | ||
Channel input voltage range | 0~600VAC Phase Voltage | |
Maximum range | 720VAC Phase Voltage | |
Digital Signal | ||
Relay output | One way electromagnetic relay output,contact capacity:3A 30V DC,3A 250V AC | |
Digital input | One way dry contact input, optocoupler isolation(5kVrms) | |
Communication | ||
RS485 communication | One way RS485 communication interface Interface type: two wire half duplex Communication baudrate: 2400bps ~ 38400bps Protocol: Modbus RTU | |
Power supply | ||
Power Supply | ME231-N-2 | ME231-N-3 |
95~265VAC/110~370VDC,45~60Hz | 24VDC | |
Maximum power consumption | 3.5VA |
Instantaneous value | |
Phase Voltage | U1,U2,U3,AVG |
Line Voltage | U12,U23,U31,AVG |
Current | I1,I2,I3,AVG,IN |
Grid Frequency | F1,F2,F3,∑ |
Power Factor PF | PF1,PF2,PF3,∑ |
Fundamental power factor DPF | DPF1,DPF2,DPF3,∑ |
Active power | P1,P2,P3,∑ |
Reactive power | Q1,Q2,Q3,∑ |
Apparent power | S1,S2,S3,∑ |
Energy | |
Active energy Pos. | EP1,EP2,EP3,∑ |
Active Energy Neg. | EP1,EP2,EP3,∑ |
Reactive Energy Pos. | EQ1,EQ2,EQ3,∑ |
Reactive energy Neg. | EQ1,EQ2,EQ3,∑ |
Apparent Energy | ES1,ES2,ES3,∑ |
Tariff Energy | ET1,ET2, ET3,ET4, ET5,ET6 |
Harmonics | |
Voltage Harmonic Distortion | THD (Total harmonic percentage), TOHD (Odd total harmonic percentage), TEHD (Even total harmonic percentage), phase L1.L2.L3 1-50th harmonic percentage, phase ABC 1-50th harmonic voltage value |
Voltage Harmonic Value | |
Current Harmonic Distortion | THD (Total harmonic percentage), TOHD (Odd total harmonic percentage), TEHD (Even total harmonic percentage), phase L1.L2.L3 1- 50th harmonic percentage, phase ABC 1-50th harmonic current value |
Current Harmonic Value | |
Phasor diagram | |
Phasor diagram | between voltage and current |
Phase Sequence | voltage and current |
Voltage Angle | U1,U2,U3 |
Current Angle | I1,I2,I3 |
UI Angle | UI1,UI2,UI3 |
Demand | |
Demand | P,Q,S |
Active power DMD Max. | P and Time |
Reactive power DMD Max. | Q and Time |
Apparent power DMD Max. | S and Time |
Unbalance | |
Voltage unbalance | Negative Sequence, zero Sequence |
current unbalance | Negative Sequence, zero Sequence |
Max.&Min. | |
Phase Voltage | U1,U2,U3,AVG |
Line Voltage | U12,U23,U31,AVG |
Current | I1,I2,I3,AVG,IN |
Active power | P1,P2,P3,∑ |
Reactive power | Q1,Q2,Q3,∑ |
Apparent power | S1,S2,S3,∑ |
Measuring accuracy | ||
current measurement accuracy | 0.1%+Accuracy of current sensor | |
Voltage measurement accuracy | ±0.2%(60V~600V AC) | |
Grid frequency | ±0.01%(45~65Hz) | |
Power factor | ±0.005 | |
Active and apparent power | IEC62053-22 level 0.5S | |
Reactive power | IEC62053-21 level 1S | |
Active energy | IEC62053-22 level 0.5S | |
Reactive energy | IEC62053-21 level 1S |