Solar DC Surge Arrester 500V 600V 800V Lightning Outdoor SPD 2 Pole DC Surge Protective Device for Solar PV Photovoltaic System Protector

Price $8.00 Compare
Min Order 600 Pieces
Shipping From Zhejiang, China
Popularity 312 people viewed
Quantity
+-
 

Taimu Electrical (Hangzhou)Co., Ltd.

VIP   Audited Supplier 2 years
Profile Certified by SGS/BV
TMSPD7
Power Source Arrester
Zinc Oxide Arrester
Tandem Arrester
AC/DC System
Small
Low Voltage
Cuboid
PBT Fireproof
ROHS, ISO9001, CE
Timelec
275V / 255V
20kA
40kA
1.5kV
IEC61643-11
IP20
Class II, T2
Timelec, OEM / Private Label brands
Carton Box
18mm
China
853620
Product Description
Product Description

SPD Surge Protective Devices are designed to protect against transient surge conditions. Large single surge events, such as lightning, can reach hundreds of thousands of volts and can cause immediate or intermittent equipment failure. However, lightning and utility power anomalies only account for 20% of transient surges. The remaining 80% of surge activity is produced internally. Although these surges may be smaller in magnitude, they occur more frequently and with continuous exposure can degrade sensitive electronic equipment within the facility.


A power surge is a brief overvoltage event that can damage electrical devices and is a common cause for the failure of electrical equipment. Surges can damage and reduce the lifespan of:

  • Heating and Air Conditioning Systems
  • Washers and Dryers
  • Water Heaters
  • Ranges & Refrigerators
  • Lighting
  • Entertainment Systems

NEW 2020 National Electrical Code Requirements
All new and renovated homes are required to be protected by Listed and Approved Type 1 or Type 2 Surge Protective Devices.

Type 1:
Permanently connected Surge Protective Device.  Protects against external and internal surges. May be installed inside or outside the home.

Type 2:
Permanently connected Surge Protective Device installed in, or next to, breaker box. Protects again internal or external surges.

Type 3:
Extra protection. Point-of-use Surge Protective Device. Must be used in conjunction with Type 1 or Type 2 SPD to meet 2020 code requirements.

Use Type 1, 2, and 3 SPDs for the best level of protection.  
 

Product Parameters
 
Max Continuous Operating VoltageUcpv500VDC600VDC1000VDC1500VDC
Nominal Discharge CurrentIn20kA20kA20kA20kA
Max Discharge Currentlmax40kA40 kA40kA40kA
Protection levelUp2.8kV3.0kV3.5kV5.5 kV
Rated shortcircuit currentIscCI100A
lcpv0.2 mA
Connection modeparalle
Response TimetA25ns
Back up fuseLT-SSD40
RemotecommunicationWith
Remote communication connection1411:NO,1112:NC
Remote contact rated current220V/0.5A
Associated disconnectors
Thermal disconnectorinternal
FusesFuses type gG100A
ground fault breakerNone
Mechnical characteristics
ConnectionBy screw terminals:6-35mm
Terminal Screw Torque2.5 Nm
RecommendedCable cross Section16mm²
Insertwire length15mm
MountingDIN rail 35mm (EN60715)
Degree of ProtectionIP20
HousingPBT
Flame retardant gradeUL94 V0
Operating temperature-40ºC~+70ºC
Operatingrelative humidity5%-95%
Working atmospheric pressure70kPa~106kPa
ConnectionBy screw terminals:6-35mm
 
Installation Instructions

Selection of SPD:
For a power distribution system, the main characteristics used to define the lightning protection system and select a SPD to protect an electrical installation in a building are:

  • SPD
    • quantity of SPD
    • type
    • level of exposure to define the SPD's maximum discharge current Imax.
  • Short circuit protection device
    • maximum discharge current Imax;
    • short-circuit current Isc at the point of installation.

The other characteristics for selection of a SPD are predefined for an electrical installation.

  • number of poles in SPD;
  • voltage protection level Up;
  • operating voltage Uc.

This sub-section Design of the electrical installation protection system describes in greater detail the criteria for selection of the protection system according to the characteristics of the installation, the equipment to be protected and the environment.


Connection of SPD:
Connections of a SPD to the loads should be as short as possible in order to reduce the value of the voltage protection level (installed Up) on the terminals of the protected equipment.

The total length of SPD connections to the network and the earth terminal block should not exceed 50 cm.

                                    SPD in plastic enclosure                                                                             SPD in metal enclosure
 

 

RED: Replace
Once the indicator shows RED, the product must be replaced.