room air conditioner
1 Years
1 Years
Portable Air Cooler
FRP
Higher
380/400 VAC
Ordinary
Server Room
in Row
10~15 years
RoHS, ISO, CE
New
DC Inverter
380/400
50/60
kstar
Carton
26.9kw, 32.7kw, 37.2kw, 41.8kw, 52.8kw, 61.7kw
China
8415812090
Product Description
StationAir Series
With the function of constant temperature and humidity, StationAir series precision air conditioners are designed with large air volume and high sensible heat ratio to meet the needs of professional computer room; The design that operation for 365 day* 24 hours non-stop efficient matches cooling system with a large area of evaporator to ensure all-weather optimal energy-saving operation.
Application: Small-medium data center, Equipment room, laboratory, storage room.
General Features
Total cooling capacity: 5kW~20kW
High power-efficiency design, EER of standard machine is above 3.0; EER of High power-efficiency machine is above 3.5
Supply upflow, downflow, upper-front flow, lower-front flow
R410 environment-friendly refrigerant
Stepless speed regulating outdoor fan system solve low frequency noise problem
Electronic expansion valve is standard equipment, and this make it more adaptive for environment
Patent fan design can reduce 30% energy. The fan supports sinking deployment and non-sinking deployment
RS485, 5-meters copper pipe, refrigerant and bracket of outdoor unit are standard equipment for cooling capacity below 12.5KW
Technical Specification
DX Unit | |||||||
ST*** | unit | 5 | 7 | ||||
Unit Configuration | - | Single Cooling | Constant Temperature | Constant Temperature and Humidity | Single Cooling | Constant Temperature | Contant Temperature and Humidity |
Total Cooling Capavity | kW | 5.5 | 7.5 | ||||
Sensible Cooling Capavity | kW | 5.2 | 6.8 | ||||
Air volume | m³/h | 2000 | 2250 | ||||
Sensible heat ratio | / | 0.95 | 0.91 | ||||
Heating capacity | KW | 3 | 3 | 3 | 3 | ||
Humidyfying capacity | kg/h | 2.5 | 2.5 | ||||
Number of compressors | Pcs | 1 | 1 | ||||
Number of Fans | Pcs | 1 | 1 | ||||
Voltage | V | 220~240 | 220~240 | 380~415 | 220~240 | 220~240 | 380~415 |
Frequency | Hz | 50 | 50 | ||||
Phase | P | 1 | 1 | 3 | 1 | 1 | 3 |
Full-load Current | A | 11.6 | 23.2 | 15.5 | 15.3 | 26.9 | 19.2 |
Unit Weight | kg | 105 | 110 | 120 | 115 | 120 | 130 |
Unit Width | mm | 550 | 550 | ||||
Unit Depth | mm | 450 | 450 | ||||
Unit Height | mm | 1750 | 1750 |
DX Unit | ||||||
ST*** | unit | 12 | 17 | 20 | ||
Unit Configuration | - | Single Cooling | Constant Temperature | Constant Temperature and Humidity | Constant Temperature | Constant Temperature and Humidity |
Total Cooling Capavity | kW | 12.5 | 17.5 | 20.5 | ||
Sensible Cooling Capavity | kW | 11.3 | 15.8 | 18.6 | ||
Air volume | m³/h | 2850 | 5000 | 6200 | ||
Sensible heat ratio | / | 0.9 | 0.9 | 0.91 | ||
Heating capacity | KW | 4 | 4 | 6 | 6 | |
Humidyfying capacity | kg/h | 4 | 4.5 | 4.5 | ||
Number of compressors | Pcs | 1 | 1 | 1 | ||
Number of Fans | Pcs | 1 | 1 | 1 | ||
Voltage | V | 380~415 | 380~415 | 380~415 | ||
Frequency | Hz | 50 | 50 | 50 | ||
Phase | P | 3 | 3 | 3 | ||
Full-load Current | A | 11.3 | 16.5 | 16.5 | 23.7 | 24.7 |
Unit Weight | kg | 165 | 170 | 180 | 280 | 300 |
Unit Width | mm | 650 | 750 | 750 | ||
Unit Depth | mm | 550 | 700 | 700 | ||
Unit Height | mm | 1850 | 1900 | 1900 |
Supporting Outdoor unit | ||||||||||||
KCS*** | unit | 7 | 10 | 18 | 24 | 28 | ||||||
Heat Exchange Capability | kw | 7.6 | 10.4 | 18.1 | 23.8 | 27.2 | ||||||
Voltage | V | 220 | 220 | 220 | 220 | 220 | ||||||
Frequency | Hz | 50 | 50 | 50 | 50 | 50 | ||||||
Phase | Pcs | 1 | 1 | 1 | 1 | 1 | ||||||
Full-load Current | A | 0.5 | 0.7 | 1.4 | 2.7 | 2.7 | ||||||
Noise | dB(A) | 38.5 | 43.9 | 43.6 | 54.9 | 52.9 | ||||||
Unit Weight | kg | 38 | 48 | 60 | 117 | 124 | ||||||
Unit Width | mm | 877 | 967 | 1014 | 1600 | 1400 | ||||||
Unit Depth | mm | 340 | 398 | 375 | 975 | 975 | ||||||
Unit Height | mm | 608 | 807 | 1244 | 650 | 650 | ||||||
Foot stool Height | mm | 455 | 455 | |||||||||
Note: parameter table. Air-cooled unit data based on 24°C,50%RH indoor return airtemperature. The noise data is sound pressure level value of 10m free field. ST005,ST007 and ST012 is prefilled refrigerant,and supplied with 5m connecting copper pipe and mounting brackets of outdoor unit. Specifications are subject to change without prior notice. |