TimeGuard Surge Protection Device T2 Class Arrester SPD 40ka 275V

Price $5.60 Compare
Min Order 60 Pieces
Shipping From Zhejiang, China
Popularity 225 people viewed
Quantity
+-
 

Taimu Electrical (Hangzhou)Co., Ltd.

VIP   Audited Supplier 2 years
Profile Certified by SGS/BV
TMSPd2
Power Source Arrester
Zinc Oxide Arrester
Tandem Arrester
AC/DC System
Small
Low Voltage
Cuboid
PBT Fireproof
ROHS, ISO9001, CE
Timelec
275V / 255V
20kA
40kA
1.5kV
IEC61643-11
IP20
Class II, T2
Timelec, OEM / Private Label brands
Carton Box
18mm
China
853620
Product Description
Product Description

SPD Surge Protective Devices are designed to protect against transient surge conditions. Large single surge events, such as lightning, can reach hundreds of thousands of volts and can cause immediate or intermittent equipment failure. However, lightning and utility power anomalies only account for 20% of transient surges. The remaining 80% of surge activity is produced internally. Although these surges may be smaller in magnitude, they occur more frequently and with continuous exposure can degrade sensitive electronic equipment within the facility.


A power surge is a brief overvoltage event that can damage electrical devices and is a common cause for the failure of electrical equipment. Surges can damage and reduce the lifespan of:

  • Heating and Air Conditioning Systems
  • Washers and Dryers
  • Water Heaters
  • Ranges & Refrigerators
  • Lighting
  • Entertainment Systems

NEW 2020 National Electrical Code Requirements
All new and renovated homes are required to be protected by Listed and Approved Type 1 or Type 2 Surge Protective Devices.

Type 1:
Permanently connected Surge Protective Device.  Protects against external and internal surges. May be installed inside or outside the home.

Type 2:
Permanently connected Surge Protective Device installed in, or next to, breaker box. Protects again internal or external surges.

Type 3:
Extra protection. Point-of-use Surge Protective Device. Must be used in conjunction with Type 1 or Type 2 SPD to meet 2020 code requirements.

Use Type 1, 2, and 3 SPDs for the best level of protection.  
 

Product Parameters
SPD according to EN 61643-11/IEC61643-11Type 2/Class II
Energy coordination with terminal equipment (10m)Type 2+ Type 3
Nominal voltage (AC) (Un)230V (50/60Hz)
 MOV (Varistors)GDT (Spark gap)
Max. continuous operating voltage (AC) (Uc)275V (50/60Hz)255V (50/60Hz)
Nominal discharge current (8/20s) (In)20KA20KA
Max. discharge current (8/20s) (Imax)40KA40KA
Voltage protection level (L-PE)/(N-PE) (Up)1.5KV1.3KV
Response time (tA)25nS
Max. mains-side overcurrent protection125AgG
Short-circuit withstand capability for max. mains-side50KA
Overcurrent protection (ISccR)
Temporary overvoltage (TOV)(UT)-- Characteristic335V/5 Sec-- withstand
Temporary overvoltage (TOV)(UT)-- Characteristic440V/120min- safe failure
Operating temperature -40C ~ +80C
Operating state /Fault indicationGreen/Red
Number of ports1
Cross-section area (min)1.5mm² solid/Flexible
Cross-section area (max)35mm² stranded /25 mm² flexible
Mounting35mm DIN rails according to EN 60715
Enclosure materials Thermoplastic , UL94 V0
Place of installationIndoor installation
IP levelIP20
Approvals TUV
Weight232.5g
 
Our Advantages


Selection of SPD:
For a power distribution system, the main characteristics used to define the lightning protection system and select a SPD to protect an electrical installation in a building are:

  • SPD
    • quantity of SPD
    • type
    • level of exposure to define the SPD's maximum discharge current Imax.
  • Short circuit protection device
    • maximum discharge current Imax;
    • short-circuit current Isc at the point of installation.

The other characteristics for selection of a SPD are predefined for an electrical installation.

  • number of poles in SPD;
  • voltage protection level Up;
  • operating voltage Uc.

This sub-section Design of the electrical installation protection system describes in greater detail the criteria for selection of the protection system according to the characteristics of the installation, the equipment to be protected and the environment.

Location and types of SPD:


Connection of SPD:
Connections of a SPD to the loads should be as short as possible in order to reduce the value of the voltage protection level (installed Up) on the terminals of the protected equipment.

The total length of SPD connections to the network and the earth terminal block should not exceed 50 cm

 

RED: Replace
Once the indicator shows RED, the product must be replaced.