Type B RCCB ELCB Price AC 63A Residual Current Circuit Breaker RCCB/RCD

Price $0.75 Compare
Min Order 240 Pieces
Shipping From Fujian, China
Popularity 241 people viewed
Quantity
+-
 

Xiamen Ninewan Trade Co., Ltd

VIP   Audited Supplier 3 years
Profile Certified by SGS/BV
BYB1E-63
-5 to +40 Degree Centigrade
Thermal/Magnetic Release
Lug Type and Pin Type
Confirming to IEC/En60898
OEM, ODM
Corton
China
8536200000
Product Description

 

 

 

 

Product Description


BYB1-63 series Residual current circuit breaker(without over-current protection) is suitable for the line of A and S 50/60Hz, voltage 240V(2pole)/415V(4pole), rated current up to 100A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will cut off the power rapidly to protect human safety and prevent the accident due to the current leakage. It can be used as infrequent changeover of the line in normal situation. It is applicable to industrial site, commercial site, tall building and civil house.

It complies with standard of IEC/EN61008.1 and GB16916.1.

Each phase of conductor at the circuit breaker passes through the zero-sequence current transformer, and the secondary side of coil connects with the electromagnetic tripper. Under normal condition, the vector sum of each phase of current passing through zero-sequence current transformer is zero. The flux of the zero-sequence current transformer is zero. And the secondary output voltage is zero and the circuit breaker doesn't zero, and the zero-sequence current transformer would produce the magnetic flux, and the secondary side of coil would output the voltage. Once the leak current increases to drive the output voltage at the secondary side to grow to certain level, the electromagnetic release would activate to drive the operation mechanism to act to break the contact that connects the power, finally to realize the leak protection.

 
Product Parameters
 
lectrical features 
Type(an aware form of the earth leakage sensed)B
Rated current In25,40,63A
Poles2P 4P
Number of poles versus modules2P= 4mod;4P=4 mod
Rated voltage Ue2P:230V~ 4P:400V~
Insulation voltage UI500V
Rated frequency50/60Hz
Rated sensitivity IAn0.03A 0.1A 0.3A
Rated residual making and breaking capacity Im500(In=25-40A)630(In=63A)
Short-circuit current lnc=lAc10000A
SCPD fuse10000
Break time under IAn≤0.1S
Rated impulse withstand voltage(1.2/50)Uimp6000V
Dielectric test voltage at and ind.Freq.for 1min2.5kV
Electrical life and Mechanical life4000
Pollution degree2
Installation 
Fault current indicatorNO
Protection degreeIP20
Ambient temperature(with a daily average of 35 )-5~+40°ºC
Storage temperature-25+70ºC
Terminal connection typeCable/U-type busbar/Pin -type busbar
Terminal size top/bottom for cable35mm²
18-3
Tightening torque3.5N*m
22
MountingOn DIN rail FN 60715 (35mm)by means of the fast clip device
ConnectionFrom top