VS1 (ZN63A-12) Vacuum Circuit Breaker, VCB 12KV, 630A, 1250A, 1600A,

Price $5000.00 Compare
Min Order 1 Piece
Shipping From Gansu, China
Popularity 291 people viewed
Quantity
+-
 

Gansu A&D Trading Co., Ltd.

VIP   Audited Supplier 15 years
Profile Certified by SGS/BV
VS1 (ZN63A-12)
High Voltage Circuit Breakers
Energy-storage Type
Normal Type Circuit Breaker
Vacuum
Trolley
Vcb
3
Circuit Breaker
CE
IEC62271-100
-15--+40 centgrade
2000M, if higher than 2000M, derate
No operating in such places as dust, smog
XD
Non-Fumigation Wooden Box
3 Phase
China
8535210000
Product Description
VS1 (ZN63A-12) indoor VCB
General Introduction

VS1 (ZN63A-12) indoor VCB is used in the circuit of 50Hz, with rated voltage up to 12KV, and with rated current from 630A to 5000A, for the control and protection of substation and equipments, and it matches with switchgear panel KYN28A and XGN.

Product Description
ItemParameters
Rated Voltage (KV) 121212121212
Rated Current (A) 630, 1250630, 1250630, 1250, 16001250, 1600, 20002000, 2500, 3150, 4000, 50003150, 4000, 5000
Rated insulation voltage1 min. Power Frequency Withstand Voltage (KV)424242424242
Rated Lightning Impulse Withstand Voltage (KV)757575757575
Rated Short-circuit Breaking Current (KA)16202531.54050
Rated Short-circuit Making Current (Peak) (KA) 40506380100130
Rated Withstand Current (Peak) (KA) 40506380100130
Rated Short-time Withstand Current (KA)16202531.54050
Breaking Times of Rated Short-circuit Making Current (Times)505050503020
Rated Duration of Short-circuit (S)444444
Rated Operating SequenceO-t-CO-180s-COO-t-CO-180s-COO-t-CO-180s-COO-t-CO-180s-COO-t-CO-180s-COO-t-CO-180s-CO
Mechanical Life (Times)200002000020000200001000010000
Rated Single Capacitor Bank Breaking Current (A)630630630630  
Rated Back-to-back Capacitor Bank Breaking Current (A)400400400400  
Standard IEC62271-100
Operation ambient temperature-15---+40 centigrade
Altitude2000 meter
Remark 1:    16KA, 20KA, 25KA, 31,5KA: t=0.3s,  and if equal or more than 40KA: t=180s
Remark 2:    Forced air cooling is needed when the rated current is equal or over 4000A
Remark 3:    No operating in such places as subject to dust, smog, corrosive/flammable gas, vapor and salt pollution.

Technical parameters of Energy Storage Motor (The Energy Storage Motor adopts permanent magnet DC motor)
ModelRated Voltage (V)Rated Output  Power (W)Normal Working Voltage Range (V)Stored Energy Time Under Rated Voltage (s)
ZYJ55-1DC110, DC220,            AC110, AC2207085%--110% Rated VoltageLess than 10