Wuhan Transformer Tan Delta Test Kit Power Dissipation Factor and Capacitance Measurements

Price $2982.00 Compare
Min Order 1 Piece
Shipping From Hubei, China
Popularity 455 people viewed
Quantity
+-
 

EP HIPOT ELECTRIC CO., LTD.

VIP   Audited Supplier 6 years
Profile Certified by SGS/BV
EPJS Series
Onsite and Remote Guidance
1 or 2 Years
<500mm
<900kg
Universal Testing Machine
0.1
LCD
Computer Control
22kg
AC220V
Build-in Thermal Printer
Frequency Conversion
0.5kv~12kv
0.1
200mA
2000va
AC 0V~50V/15A
45Hz/55Hz 47.5Hz/52.5Hz 55Hz/65Hz 57.5Hz/62.5Hz
0.001%
0.001PF
+-(Reading*1.0%+0.040%)
+-(Reading*1.0%+1.00PF)
Without Limit
15PF Less Cx Less 300NF
Cx Less 30 NF
EP Hipot Electric
Plywood Case with Foam and Waterproof Plastics
460*360*350mm
Wuhan, China
9031809090
Product Description
Wuhan Transformer Tan Delta test kit power dissipation factor and capacitance measurements
 
 
Product Description

General Information:
EPJS-6000 is a new generation, fully automatic on-site measure dielectric loss(tgδ)and the capacitance (Cx) of electric equipment. It's suitable for testing on transformer, insulating bush, capacitor, CT/PT, MOA etc.

 

Product Parameters

Features:

  • Build-in dielectric loss bridge, frequency conversion power supply, testing transformer, SF6 high stability standard capacitor.
 
  • The test high-voltage source is generated by the inverter inside the instrument and is used for the test object after boosting the voltage from the transformer.
 
  • Frequency can be changed into 50Hz, 47.5Hz/52.5Hz, 45Hz/55Hz, 60Hz, 57.5Hz/62.5Hz, 55Hz/65Hz. Digital notch technology is adopted to avoid the interference of power frequency electric field to the test.
 
  • Multiple protection of input voltage fluctuation, output short circuit, over-voltage, over-current, temperature, secure and reliable. Meanwhile, it has the function of grounding testing, that voltage boost is not permitted for non-grounding equipment.
 
  • LCD touch screen display. English menu easy to operate.
 
  • 200 groups' data storage. Save testing result according to time order, check history record and print the result.
 
  • Multiple testing mode, with modes of inside high voltage, outside high voltage, inner standard, external standard, GST/UST, self-excitation. High voltage (more than 12kV) dielectric loss test can be made in the situation of external standard outside high voltage.
 
  • Test full sealed CVT (Capacitive Voltage Transformer) C1 and C2 dielectric loss and capacitance at the same time. Also test CVT transformation ratio and voltage angle difference.
 
  • The instrument can accurately measure the CVT dielectric loss value and capacitance value without removing the CVT high voltage lead.
 
  • The dielectric loss and capacitance value of C0 in the upper end of CVT can be measured by using the reverse shielding method.
 
  • High speed sampling signal. Inverter and sampling circuit inside are digitized controlled. Output voltage is adjusted continuously.
Technical Specifications:
Working condition-15ºC~40ºCRH<80%
Anti-interference principleFrequency conversion
Power supplyAC 85V~160VGenerator can be used
High voltage output0.5kV~12kVEvery 0.1kV
Precision2%
Maximum current 200mA
Capacity2000VA
Self-excitation powerAC 0V~50V/15A45HZ/55HZ 47.5HZ/52.5HZ
55HZ/65HZ 57.5HZ/62.5HZ
Automatic double frequency
Resolutiontgδ: 0.001%  Cx: 0.001pF
Accuracy△tgδ:±(Reading*1.0%+0.040%)
△Cx :±(Reading*1.0%+1.00PF)
Measurement rangetgδWithout limit
Cx15pF < Cx < 300nF
12kVCx < 30  nF
5kV Cx < 150 nF
1kVCx <300 nF
CVT testCx < 300 nF
CVT ratio range10~10000
CVT ratio accuracy0.1%
CVT ratio resolution0.01
Storage200 group supports U disk data storage
DimensionMain unit: 350(L)×270(W)×270(H)
Accessory box: 350(L)×270(W)×160(H)
WeightMain unit: 22.75kg
Accessory box: 5.25kg
Certifications

Packaging & Shipping

Installation Instructions

Company Profile

FAQ


 



More details on 12kV C&DF Tester please contact EPHipot Electric, we have professional tech team to design correctly designed products and systems.



Message Type
* Message Content
* Name  
* Phone
* Email
* CAPTCHA