Zw32-12 Type Pole-Mounted Circuit Breakers Integral Sealed Poles Recloser

Price $3000.00 Compare
Min Order 2 Pieces
Shipping From Zhejiang, China
Popularity 270 people viewed
Quantity
+-
 

Yueqing Liyond Electric Co., Ltd.

VIP   Audited Supplier 16 years
Profile Certified by SGS/BV
ZW32-12
High Voltage Circuit Breakers
Manual Type
Normal Type Circuit Breaker
Vacuum
Fixed
Auto Recloser
3
Circuit Breaker
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
ISO9001-2000
12kv
630A
Outdoor
Vacuum
20/25/31.5ka
10000 Times
Liyond
Standard Export Packaging
as specification
China
Product Description


 

Designed on the basis of ZW32 vacuum circuit breaker, the integrated solid-sealed pole combines a variety of advanced power equipment construction technology, micro-power electronic sensing technology, wireless communication technology, on-line power collection technology, etc.; up to 11 integrated voltage and current sensors (power-side three-phase voltage, load-side three-phase voltage, three-phase current, zero-sequence voltage and zero-sequence current). Single-phase power 10W, less than 10pC local discharge, side and bottom operation windows, more convenient operation.

The main configuration of ZW32 circuit breaker includes line online monitoring software, mobile phone APP, energy extraction unit, FTU automation terminal, and deeply fused circuit breaker. The product is widely used in 10kV urban and rural distribution overhead ring network line for dividing, sectioning and contacting switches, and it can realise the automated switching device for load deployment of the ring network line.

 

 

Main technical parameters of circuit breaker

S/NItemUnitData
1Rated voltagekV12
2Rated currentA630
31min power frequency withstand voltageDry test: phase to phase, ground/fracturekV42/48
Wet test: phase to phase, ground/fracturekV34
4Lightning impulse withstand voltage (peak value) phase to phase, ground/fracturekV75/85
5Rated short circuit breaking currentkV20/25
6Rated short circuit making current (peak value)kA50/63
7Rated peak withstand currentkA50/63
84s short-term withstand currentkA20/25
9Rated operating sequence-O-0.3s-CO-180s-CO
10Rated short circuit current breaking timestimes30
11Mechanical lifetimes10000
12Energy storage motor rated voltageVDC24
13Energy storage motor rated powerW70
14Rated operating voltageVDC24
15Energy storage time at rated voltageS<10
16Partial discharge of the whole machinePc<10

 


Normal use conditions
1. Altitude not exceeding 1000m;
2. Ambient temperature not exceeding ±40°C;
3. Seismic intensity not exceeding 8 degrees;
4. Maximum wind speed should not exceed 35m/s. 
5. There should be no explosion, no corrosive harmful gas that destroys insulation, and no violent vibration;
6. the thickness of ice cover does not exceed 10mm.
For special conditions of use, please make specific instructions at the time of ordering, so that the insulation level and other capabilities of the circuit breaker can be corrected. Specific parameters are subject to actual delivery.

 

Application

Instructions for ordering
1) Model, name and quantity of circuit breaker;
2) Rated voltage, rated current and rated short-circuit breaking current of the circuit breaker;
3) Operation mode of operating mechanism (manual, electric, with remote control), type and rated value of operating power supply;
4) Current transformer accuracy level, ratio, quantity;
5) Name and quantity of spare parts;
6) Other special requirements.