Dry Type Transformer Application:
Epoxy resin cast dry-type power transformers are cast using advanced technology, with high product reliability and long service life. And protective shells can be added according to different protection levels. It is suitable for important or special environment places such as high-rise buildings, commercial centers, airports, tunnels, chemical plants, nuclear power plants, etc.
The core is made of high-performance cold-rolled oriented silicon steel sheets and a fully automatic robot lamination machine. It has small shearing burrs and low lamination coefficient, which effectively reduces the no-load loss, no-load current and noise of the transformer. No-load loss is 5%~10% lower than manual lamination.
Dry Type Transformer Application:
Apply to power plant (station), substation (power distribution station) and industrial etc.
Dry Type Vacuum Cast Resin Transformer Specifications:
Capacity: 30kVA~ 2500 kVA
Primary side rated voltage: 6kV~ 35kVA
Secondary side rated voltage: 0.4kV
Tap changer position : 5
Frequency:50/60Hz
Phase: three phases
Connection group: Dyn11/Yyn0 etc.
Impedance: 4%~6%
Dry Transformer Advantage:
1. Safety: Since dry transformers do not contain flammable or toxic liquids that can leak or catch fire.
2. Environmental protection: type power transformers do not use harmful liquids or liquids to work, so they will not release harmful gases into the environment causing greenhouse effect.
3. Low noise: due to the use of laminated iron core technology and multiple layers of insulating paint on the outside of the iron core, the noise of the cast resin dry type transformer is reduced.
4. Low loss: dry-type transformer adopts higher grade silicon steel sheet, which belongs to high energy efficiency grade transformer, the no-load loss is 15% lower than SCB12 transformer, and the load loss is 10% lower than SCB12 transformer
5. Low installation cost: small size, light weight, less space occupation, no need for fire extinguishing system and low installation cost.
6. Maintenance: Since the dry-type transformer does not use liquid for filling and the use of accessories, it requires almost no maintenance.
7. Sustainability: small partial discharge (usually below 10PC), high reliability, long-term safe operation can be guaranteed, and the service life can reach 30 years.
8. Good heat dissipation effect: the composite insulation composed of pure resin and glass fiber has extremely high electrical strength, which improves the heat dissipation efficiency of the winding surface.
Rated capacity (kVA) | VoltageCombination (kV) | Connection Symbol | 13Type Loss(W) | No-load current (%) | Impedance (%) | ||
HV | LV | No Load | On Load(120ºC) | ||||
30 | 35 38.5 ±5% or ±2 x2.5% | 0.4 | Dyn11 or Yyn0 | 360 | 1140 | 2.8 | 6 |
50 | 450 | 1425 | 2.6 | ||||
80 | 540 | 1805 | 2.2 | ||||
100 | 630 | 2090 | 2 | ||||
125 | 700 | 2420 | 1.8 | ||||
160 | 790 | 2810 | 1.8 | ||||
200 | 880 | 3325 | 1.6 | ||||
250 | 990 | 3800 | 1.6 | ||||
315 | 1175 | 4510 | 1.4 | ||||
400 | 1375 | 5415 | 1.4 | ||||
500 | 1620 | 6650 | 1.4 | ||||
630 | 1860 | 7695 | 1.2 | ||||
800 | 2160 | 9120 | 1.2 | ||||
1000 | 2430 | 10450 | 1 | ||||
1250 | 2835 | 12730 | 1 | ||||
1600 | 3240 | 15485 | 0.8 | ||||
2000 | 3825 | 18240 | 0.7 | ||||
2500 | 4455 | 21850 | 0.7 |